期刊文献+

组合屏蔽层对电力变压器杂散损耗的影响 被引量:4

Influence of Combination Shielding Layers on Stray Losses of Single-Phase Power Transformer
下载PDF
导出
摘要 大容量单相电力变压器的箱体杂散损耗影响变压器效率和可靠性。通常采用箱体内壁敷设铁磁层的方法降低损耗,但铁磁叠片边界会使箱体局部磁场增强并产生局部过热。为此提出利用铁磁和非磁性导电层的不同组合屏蔽方法,并通过有限元仿真分析箱体和屏蔽层损耗,分析结果表明在优化屏蔽层厚度条件下纯导电层表面敷设一层铁磁材料,能有效降低总杂散损耗。 Stray loss of large single phase power transformer tank influenced its efficiency and reliability.Magnetic material was usually attached on the inner wall of the transformer tank in order to reduce the stray loss.However,the magnetic field surrounding the ferromagnetic shielding was enhanced and resulted in local overheat of the tank.Various structures of ferro-and/or non-magnetic thin-layers are proposed and modeled by2D and3D finite element analysis(FEA).Simulation results showed that the stray losses could be effectively reduced by using non magnetically metallic layer between ferromagnetic layer and tank wall with optimal shielding thickness.
作者 葛康 谢宝昌 GE Kang;XIE Bao-chang(School of Electronic Information and Electrical Engineering, Shanghai Jiaotong University, Shanghai 200240, P. R. China)
出处 《科学技术与工程》 北大核心 2017年第36期75-81,共7页 Science Technology and Engineering
关键词 单相电力变压器 组合屏蔽层 杂散损耗 有限元分析 single-phase power transformer combination shielding layers stray loss finite element analysis
  • 相关文献

参考文献3

二级参考文献26

  • 1李季,罗隆福,许加柱.电力机车主变压器油箱损耗的三维有限元分析[J].高压电器,2005,41(3):186-187. 被引量:11
  • 2王建华,黄娟.电力变压器直流电阻测量值超标原因分析及解决对策[J].高压电器,2007,43(3):239-240. 被引量:7
  • 3Cheng Z, Takahashi N, Yang S, et al. Loss spectrum and electromagnetic behavior of problem 21 family[J]. IEEE Trans.Magn. ,2006,42(4) : 1467-1470. 被引量:1
  • 4Biro O, Preis K, Ticar I. A FEM method for eddy cur- rent analysis in laminated media [J]. COMPEL,2005,24 (1) :241-248. 被引量:1
  • 5Cheng Z, Hu Q, Jiao C, et al. Laminated core models for determining exciting power and saturation character- istics[J]. ICEF,2008,21 ( 1 ) :415-418. 被引量:1
  • 6Miyagi D, Yoshida T, Nakano M, et al. Development of measuring equipment of DC-biased magnetic properties using open-type single-sheet tester[J]. IEEE Trans. Magn, 2006,42(10) :2846-2848. 被引量:1
  • 7Nakata T, Ishihara Y, Nakano M. Iron losses of silion steel core produced by distored flux [J]. Elect.Eng. in Jap, 1970,90( 1 ) : 10-20. 被引量:1
  • 8PAVLIK D,JOHNSON D C.Calculation and reduction of stray and eddy losses in core-form transformers using a highly accurate finite element modeling technique[J]. IEEE Transactions on Power Delivery, 1993,8(1):239-245. 被引量:1
  • 9ERICH S, PETER H. Design optimization of power transformers,part 2-eddy current analyses for tank wall and core clamping parts [C]//International Conference on Power System Technology. [S.l.] :IEEE, 2004 : 1375-1380. 被引量:1
  • 10XIE D X,TANG Y Q,XU Z H.FEM analysis of 3D eddy current field in power transformer[J]. IEEE Transactions onMagnetics, 1987,23(5) :3786-3788. 被引量:1