热风供暖房间室外冷风水平作用范围的实测研究

Horizontal influence range of outdoor infiltration cold air in warm-air heating rooms
下载PDF
导出
摘要 实测研究了室外冷风侵入对碰撞射流通风(IJV)和混合通风(MV)供暖房间近地面温度分布的影响。结果表明:IJV供暖时,送风热气流对近地面空气温度的控制能力强于MV供暖,并且前者近地面的空气温度远高于后者;IJV和MV供暖房间近地面的温度分布均不受冷风侵入频率的影响,前者受冷风的影响范围随冷风侵入量的减小而减小,而后者任意冷风侵入量下的冷风均覆盖于整个地面。通过设置适当的送风参数可使IJV供暖房间受室外冷风的影响程度和范围缩小,并存在基本消除室内热力分层的可能性,但MV供暖基本不可能实现这些目的。 Experimentally studies the effect of outdoor infiltration cold air on the air temperature distribution near the ground in the impinging jet ventilation (IJV) and mixing ventilation (MV) heating rooms, respectively. The measured results indicate that the control capability of the warm supply air for the floor temperature in IJV heating room is stronger than that in MV heating room, and the air temperature near the ground in the former is much higher than that in the latter. The temperatures near the ground in both IJV and MV heating rooms are not affected by the frequency of outdoor infiltration cold air, and the influence range of the infiltration cold air decreases with decreased amount of outdoor air in IJV heating room, while the infiltration cold air distributes along the whole ground for any amount of outdoor cold air in MV heating room. By setting the appropriate supply air parameters, the influence degree and range of the infiltration cold air can be decreased and the indoor thermal stratification may be eliminated for IJV, but for MV there is no possibility to achieve these purposes.
作者 叶筱 亢燕铭 华凤皎 钟珂 Ye Xiao;Kang Yanming;Hua Fengjiao;Zhong Ke(Donghua University, Shanghai, Chin)
机构地区 东华大学
出处 《暖通空调》 2018年第5期116-121,共6页 Heating Ventilating & Air Conditioning
基金 国家自然科学基金资助项目(编号:51278094)
关键词 冷风侵入 碰撞射流通风 混合通风 影响范围 热力分层 热风供暖 cold air infiltration, impinging jet ventilation, mixing ventilation, influence range, thermal stratification, warm-air heating
  • 相关文献

参考文献4

二级参考文献21

  • 1赵荣义.空气调节[M]. 4版.北京:中国建筑工业出版社,2009:118 -121. 被引量:12
  • 2ZHAO B,ZHANG Y,LI X T,et al.Comparison of indoor aerosol particle concentration and deposition in different ventilated rooms by numerical method[J].Building and Environment,2004,39(1):1-8. 被引量:1
  • 3KARIMIPANAH T,AWBI H B.Theoretical and experimental investigation of impinging jet ventilation and comparison with wall displacement ventilation[J].Building and Environment,2002,37(12):1329-1342. 被引量:1
  • 4CHEN H J,MOSHFEGH B,CEHLIN M.Investigation on the flow and thermal behavior of impinging jet ventilation systems in an office with different heat loads[J].Building and Environment,2013,59:127-144. 被引量:1
  • 5VARODOMPUN J,NAVVAB M.HVAC ventilation strategies:The contribution for thermal comfort,energy efficiency,and indoor air quality[J].Journal of Green Building,2007,2(2):131-150. 被引量:1
  • 6MORAWSKA L,SALTHAMMER T.Indoor environment[J].Weinhein:Wiley-VCH,2003. 被引量:1
  • 7WILLIAM W N,GLEN R C.Mass-transport aspects of pollutant removal at indoor surfaces[J].Environment International,1989,15(1/2/3/4/5/6):567-584. 被引量:1
  • 8CHUNG K C,HSU S P.Effect of ventilation pattern on room air and contaminant distribution[J].Building and Environment,2001,36(9):989-998. 被引量:1
  • 9COSTA J J,OLIVEIRA L A,BLAY D.Turbulent airflow in a room with a two-jet heating-ventilation system:A numerical parametric study[J].Energy and Building,2000,32(3):327-343. 被引量:1
  • 10GB 50736—2012民用建筑供暖通风与空调设计规范[S].北京:中国建筑工业出版社,2012. 被引量:1