期刊文献+

温度对交流无间隙金属氧化物避雷器状态检测的影响 被引量:5

Influence of Temperature on Condition Detection of AC MOA without Gaps
原文传递
导出
摘要 随着氧化物非线性电阻片配方工艺的不断改进,其特性对温度的敏感程度也有显著变化。通过对国内金属氧化物避雷器生产厂家不同规格的氧化锌非线性电阻片进行的温度特性试验研究,分析了不同温度下避雷器状态检测特征参量的变化规律,以期对状态检测的有效性和状态评估提供参考。研究发现,离线状态检测测得的0.75倍直流参考电压下泄漏电流以及在线状态检测测得的阻性电流基波分量随温度变化最为明显。 With the progress of the metal oxide varistor (MOV) formula and technology, the sensi- tivity of temperature characteristics has changed significantly. Different types of MOV from factories in China are tested to measure the characteristic parameters of the condition detection at different tempera- tures. The regularity is extracted after analyzing the results to provide a reference for the validity of metal oxide arrester (MOA) condition detection. It is found that the leakage current under 0.75 times of the DC reference voltage measured by off-line detection and the fundamental component of the resistive current measured by on-line detection changes the most obviously with temperature.
出处 《电瓷避雷器》 CAS 北大核心 2017年第6期57-61,共5页 Insulators and Surge Arresters
基金 国家电网公司科技项目(编号:520940150004)
关键词 全属氧化物避雷器 温度特性 状态检测 泄漏电流 基波分量 MOA temperature characteristics condition detection leakage current fundamentalcomponent
  • 相关文献

参考文献19

二级参考文献104

共引文献407

同被引文献70

引证文献5

二级引证文献9

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部