期刊文献+

受限空间开口对细水雾灭火有效性影响实验研究 被引量:2

Experimental study on influence of opening in confined space on suppression effectiveness of water mist
下载PDF
导出
摘要 为了探讨开口的位置与尺寸对受限空间内的细水雾灭火有效性的影响,设计了一个尺寸为1.2 m×1.2 m×1.2 m的特殊受限空间模拟实验台,开展了一系列细水雾灭火对比实验,测量了烟气温度以及灭火时间等实验参数,通过改变实验燃料、火源功率、开口尺寸、开口位置等因素来研究开口对特殊受限空间内细水雾灭火有效性的影响规律。结果表明:在特殊受限空间内,相同条件下,开口位置由下至上,细水雾抑制火灾有效性由低至高;开口尺寸由大至小,细水雾抑制火灾有效性由高至低。当开口尺寸足够小以后,细水雾抑制火灾有效性反而会逐渐增强。 In order to investigate the influence of the position and size of opening in the confined space on the fire suppression effectiveness of water mist,a simulation experimental platform for the specific confined space with the size of 1. 2 m × 1.2 m × 1. 2 m was designed. A series of contrastive experiments on the fire suppression by water mist were conducted and some experimental parameters such as smoke layer temperature and fire-extinguishing time were measured,then the influence of opening on the fire suppression effectiveness of water mist in the specific confined space was studied through changing some factors such as the fuel type,the heat release rate of fire source,and the size and position of opening. The results showed that the fire suppression effectiveness of water mist increases with the higher opening position and the bigger opening size under the same experimental conditions in the special confined space. However,the fire suppression effectiveness of water mist increases when the opening size is small enough.
出处 《中国安全生产科学技术》 CAS CSCD 北大核心 2017年第11期135-142,共8页 Journal of Safety Science and Technology
基金 湖南省自然科学基金青年基金项目(2017JJ3392) 中国博士后科学基金面上项目(2016 M602430) 中国科学技术大学火灾科学国家重点实验室开放课题(HZ2016-KF04)
关键词 细水雾 灭火有效性 受限空间 开口位置 开口尺寸 water mist fire suppression effectiveness confined space opening position opening size
  • 相关文献

参考文献6

二级参考文献22

  • 1王蔚,张和平,杨昀,徐亮.全尺寸多功能热释放速率实验台的设计[J].消防科学与技术,2004,23(6):521-524. 被引量:7
  • 2陆强,李钙,廖光煊,黄鑫,朱伟.油池火中细水雾强化火焰现象的研究[J].中国工程科学,2006,8(7):78-82. 被引量:18
  • 3刘江虹 廖光煊 等.细水雾与固体火焰相互作用模拟研究[M].合肥:中国科学技术大学,2002.. 被引量:2
  • 4NFPA 750. Standard for Water Mist Fire Suppression Systems [ S ]. 2000. 被引量:1
  • 5Liu Zhigang, Andrew K Kim. A review of the research and application of water mist fire suppression systems-fundamental studies [J]. Journal of Fire Protection Engineering,2000, 10(3) :32-50. 被引量:1
  • 6Wang Xishi, Liao Guangxuan, Yao Bin, et al. Preliminary study on the interaction of water mist with pool fires [ J ].Journal of Fire Sciences, 2001, 19(1) :45-60. 被引量:1
  • 7Lefebvre A H. Atomization and Sprays [ M ]. New York:Taylor & Francis, 1989. 被引量:1
  • 8Linville Jim L. SFPE Handbook of Fire Protection Engineering [ M ]. Quincy: National Fire Protection Association,1995. 被引量:1
  • 9Wighus R. Extinguishment of enclosed gas fires with water spray[ C]//Proceedings of the Third International Symposium on Fire Safety Science. Edinburgh, Scotland, 1991:997-1006. 被引量:1
  • 10Orloff L, De Ris J. Froude modeling of pool fires [ C ]//Nineteenth Symposium (International) on Combustion. Pittsburgh, 1982: 885-895. 被引量:1