摘要
分析了地暖系统与散热器系统并网时容易出现的一些问题,找到导致问题发生的根本原因是供水温度太高。提出通过控制室外管网压差,在回水管增设平衡阀,把混水泵用水力引射装置代替等三种措施来降低地暖系统的供水温度。最后通过工程应用对混水装置做了简要分析。
Problems of connection of floor heating system and radiator system were analyzed, which is due to high supply water temperature. There measures, including controlling pressure difference of outdoor network, adding balance valve in return pipe, replacing water pump with hydraulic ejector, were proposed to cut down the supply water temperature. Finally, a brief analysis of the mixing device was made by engineering application.
出处
《建筑热能通风空调》
2017年第6期87-89,共3页
Building Energy & Environment
关键词
地板采暖
供水温度
平衡阀
混水装置
floor heating, water supply temperature, balance valve, mixing device