期刊文献+

提高下垂控制逆变器虚拟功角暂态稳定性的控制方法 被引量:23

Control Methods for Improving Virtual Power Angle Transient Stability of Droop-controlled Inverters
下载PDF
导出
摘要 下垂控制逆变器在大扰动下存在类似于传统同步发电机的暂态失稳现象,且受到逆变器输出电流限幅环节的影响使其电压控制环失去作用,因而工作于饱和电流源模式。文中进一步分析了在暂态过程中由于电压非理想跟踪特性而导致虚拟功角曲线发生偏移、并使逆变器暂态稳定裕度下降的机理。在此基础上,提出一种估计逆变器输出电流并用于前馈控制的方法,以提高逆变器的电压跟踪性能,从而提高逆变器的暂态稳定性。此外,针对逆变器暂态过程中无稳定平衡点的问题,提出一种暂态同步控制策略。当逆变器电压控制环饱和失控时,将逆变器控制在合适的平衡点,以防止其发生暂态失稳,同时为系统提供无功支持。最后,采用单机无穷大系统验证了所提出方法的有效性。 Like synchronous generators,transient instability also occurs to droop-controlled inverters when subjected to large disturbances.Owing to the current limitation,the voltage loop of the inverter is out of work during the disturbance and the inverter turns to operating in the current source mode.The mechanism of the virtual power angle curves deviating during the transient process because of the limited voltage tracking performance,which reduces the stability margin,is further analyzed.To this end,a current feed-forward control method based on estimating the output current is proposed to improve the voltage tracking performance so that the transient stability is improved.Besides,to deal with the loss of equilibrium points during the transient process,a transient synchronous control method is proposed.It helps the inverter to reach a proper equilibrium point when the voltage loop is out of commission and prevents the inverter from transient instability.Finally,simulations on a singlemachine-infinite-bus system verify the effectiveness of the proposed control methods.
出处 《电力系统自动化》 EI CSCD 北大核心 2017年第12期56-62,99,共8页 Automation of Electric Power Systems
基金 国家重点研发计划资助项目(2016YFB0900104) 国家自然科学基金资助项目(51577168) 云南电网科技项目(yndw(2016)000303DD00124)~~
关键词 逆变器 虚拟功角 暂态稳定 电流限幅 电流前馈控制 下垂控制 inverter virtual power angle transient stability current limiting current feed-forward control droop control
  • 相关文献

参考文献4

二级参考文献78

  • 1刘伟达,孟建良,庞春江,蔡媛媛.多Agent在电力系统中的应用[J].电气时代,2004(8):72-74. 被引量:11
  • 2周凤起.中国可再生能源发展战略[J].石油化工技术经济,2005,21(4):1-6. 被引量:16
  • 3王兆安,黄俊.电力电子技术[M].北京:机械工业出版社.2008. 被引量:61
  • 4TIRUMALA R,MOHAN N,HENZE C.Seamless transfer ofgrid-connected PWM inverters between utility-interactive andstand-alone modes[C]//Proceedings of the 17th Annual IEEEApplied Power Electronics Conference and Exposition:Vol 2,March 10-14,2002,Dallas,TX,USA:1081-1086. 被引量:1
  • 5POGAKU N,PRODANOVIC M,GREEN T C.Modeling,analysis and testing of autonomous operation of an inverter-based microgrid[J].IEEE Trans on Power Electronics,2007,22(2):613-625. 被引量:1
  • 6LASSETER R H,PAIGI P.Microgrid:a conceptual solution[C]//Proceedings of IEEE the 35th Annual Power ElectronicsSpecialists Conference:Vol 6,June 20-25,2004,Aachen,Germany:4285-4290. 被引量:1
  • 7LI Y,VILATHGAMUWA D M,LOH P C.Design,analysis,and real-time testing of a controller for multibus microgridsystem[J].IEEE Trans on Power Electronics,2004,19(5):1195-1204. 被引量:1
  • 8GUERRERO J M,VASQUEZ J C,MATAS J,et al.Controlstrategy for flexible microgrid based on parallel line-interactiveUPS systems[J].IEEE Trans on Industrial Electronics,2009,56(3):726-736. 被引量:1
  • 9AHN S J,PARK J W,MOON S I,et al.Power-sharingmethod of multiple distributed generators considering controlmodes and configurations of a microgrid[J].IEEE Trans onPower Delivery,2010,25(3):2007-2016. 被引量:1
  • 10BOLLEN M H J,SANNINO A.Voltage control withinverter-based distributed generation[J].IEEE Trans onPower Delivery,2005,20(1):519-520. 被引量:1