期刊文献+

基于机理模型的汽温控制系统优化及应用 被引量:1

Optimization and Application of Steam Temperature Control System Based on Mechanism Model
下载PDF
导出
摘要 针对火电机组过热汽温控制的难点和要求,常规串级控制系统无法达到良好控制效果,尤其在大范围变负荷过程中很难控制汽温动态偏差在要求范围内。分析了基于机理模型的双回路汽温控制原理和控制参数整定方法,并对控制方案进行优化。应用于某300 MW CFB机组过热汽温控制,结果表明其稳态和动态控制品质良好,并能适应机组大范围变负荷需要。由于控制方案能够灵活配置汽温控制中惰性区传递函数时间常数和对控制器参数进行增益调整,因此在工程应用中具有很好的推广作用。 This paper focuses on difficulties of the super heating steam temperature control for thermal power units and requirements. Conventional cascade control system can not achieve good control effect, especially in the wide range of load change. It is difficult to control the steam temperature deviation in the dynamic requirements. The article analyzes the double loop based on mechanism model steam temperature control principle and control parameter setting method. It also optimizes the control scheme. It is applied to the su- per heated steam temperature control of 300 MW CFB unit. the results show that the steady state performance and the dynamic perform- ance have good quality and it can adapt to the wide range of load change. The control scheme can flexibly configure the time constant of the inertia transfer function in the steam temperature control and adjust the gain of the controller parameters. It has a good promotion in engineering applications.
出处 《东北电力技术》 2017年第4期39-41,51,共4页 Northeast Electric Power Technology
关键词 双回路 过热汽温 PTn环节 焓差 变负荷 double loop super heating steam temperature PTn module enthalpy deviation load change
  • 相关文献

参考文献9

二级参考文献50

共引文献95

同被引文献1

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部