摘要 为研究混凝土冷辐射板的传热情况并对其供冷能力进行分析,采用RC简化传热模型建立混凝土辐射板二维稳态的传热模型,对混凝土辐射板内部传热情况进行模拟,计算得到混凝土内部及表面温度场.根据计算结果分析不同供水温度、埋管间距情况下,冷顶板表面的温度分布情况及供冷能力.经过实验验证,RC简化传热模型对板内温度和供冷能力的计算误差小于6%;混凝土冷辐射板供冷能力受供水水温、埋管间距及流量的直接影响,当供水温度为11~14℃,总流量为0.26~0.33m^3/h,室内空气温度为25~26℃时,混凝土辐射板平均供冷量为40~50 W/m^2. This paper aims to study the characteristics of heat transfer for concrete radiant ceiling and its cooling capacity. A two-dimensional stead-state heat transfer model on the basis of simplified RC (Resistance and Capacity) Method was adopted to simulate the inner heat-transfer condition of concrete ceiling as well as the temperature fields. The calculated results showed that the cooling capacity of concrete radiant ceiling was affected by the temperature of supply water, distance of tubes and water flow rate. When the supply water temperature, flow rate and indoor air temperature ranged from 11-14 ℃, 0.26 t0.33 m^3/h and 25-26℃, respectively, the cooling capacity varied from 40 to 50 W/m^2. The simulation models were also validated by experimental results, and the calculation error was less than 6%.
作者 李念平 潘楚阳 黄小君 顾昭阳 苏林 常丽娜 LI Nianping PAN Chuyang HUANG Xiaojun GU Zhaoyang SU Ling CHANG Lina(College of Civil Engineering, Hunan University, Changsha 410082, China)
出处 《湖南大学学报(自然科学版)》 EI CAS CSCD 北大核心 2017年第3期143-150,共8页 Journal of Hunan University:Natural Sciences
基金 国家自然科学基金资助项目(71578220)~~
关键词 混凝土辐射冷顶板 RC简化传热模型 稳态传热 供冷能力 实验测试 concrete radiant cooling panel simplified RC model steady-state heat transfers cooling capacity experimental tests
  • 相关文献

参考文献5

二级参考文献14

  • 1刘学来,李永安.毛细管平面辐射空调传热特性的研究[C]//山东,2011年全国冷冻冷藏行业与山东制冷空调行业年会暨绿色低碳新技术研讨会,2011. 被引量:2
  • 2FEUSTEL H E,STETIU C. H ydronic radiant cooling-prelimi- nary assessment[J]. Energy and Buildings, 1995,22(3) : 193 - 205. 被引量:1
  • 3IMANARI T,OMORI T, BOGAKI K. Thermal comfort and energy consumption of the radiant ceiling panel system, com- parison with the conventional all-air system[J]. Energy and Buildings, 1999,30(2) :167-175. 被引量:1
  • 4KILKIS L B, SAGER S S, ULUDAG M. A simplified model for radiant heating and cooling panels[J]. Simulation Practice and Theory, I994,2(2): 61-76. 被引量:1
  • 5ARDEHALI M M, PANAH N G, SMITH T F,et al. Proof of concept modeling of energy transfer mechanisms for radiant conditioning panels[J]. Energy Convection and Management, 2004,45(13/14) : 2005-2017. 被引量:1
  • 6KARADAG Refer. New approach revelant to total heat trans- fer coefficient including the effect of radiation and convection at the ceiling in a cooled ceiling r0om[J]. Applied Thermal Engi- neering, 2009,29 (8) .. 1561 - 1565. 被引量:1
  • 7MIRIEL J, SERRES L, TROMBE A. Radiant ceiling panel heating-cooling systems: experimental and simulated study of the performances, thermal comfort and energy consumptions [J]. Applied Thermal Engineering, 2002, 22 (16) : 1861 - 1873. 被引量:1
  • 8INCROPERA F P, DEWITTE D P. Fundamentals of heat and mass transfer[M]. New York, Wiley,1991. 被引量:1
  • 9MINT C, SCHUTRUM L F, PARMELEE G V, etal. Nat ural convection and radiation in a panel heated room[J] ASHRAE Transactions, 1956,62 (1) .. 337- 358. 被引量:1
  • 10刘英杰,刘乃玲,蔡芳芳,王如国.辐射供冷系统末端形式对比及发展研究[J].节能,2008,27(9):26-29. 被引量:3

共引文献15

同被引文献5

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部