期刊文献+

一种基于变步长差分的电压暂降检测方法 被引量:1

A Voltage Sag Detection Method Based on Variable Step Difference
下载PDF
导出
摘要 电压暂降的实时、准确检测是快速补偿的前提,但频率偏移下基于软件锁相环的检测方法无法准确地检测出相位跳变角。基于αβ-dq变换,提出利用变步长差分来构造出电压的αβ分量,采用恒定50Hz单位正、余弦信号瞬时采样值来构成αβ-dq变换阵,从而计算出电压幅值与相位跳变角,避免了锁相保持给相位跳变角带来的测量误差。并就谐波、噪声及频率偏移等影响因素,对改进方法进行了详细的检测特性分析。理论分析和仿真结果表明,基于变步长差分的改进检测方法,实现方式简单且计算量小,无需同步锁相,可通过调节检测点间隔满足实时性与精确度的不同要求。 The quick and accurate detection of voltage sag is the premise of fast compensation, but under the condition of frequency offset, the phase jump angle is hard to be detected precisely by the software phase locked loop. Based on αβ- dq transform, a detection method by utilizing variable- step difference is proposed to generate αβ components of voltage in this paper. By using instantaneous sample values of the constant 50Hz sine and cosine signals to form αβ- dq trans- form matrix, Voltage amplitude and phase jump angle can be calculated, which avoids the measurement error in phase jump angle caused by phase lock holding. The detecting characteristics for such influence factors as harmonics, noise and frequency offset are analyzed in detail by using modified methods. Theoretical analysis and simulation results show that the improved method based on variable-step difference has such advantages as easy realization mode and less calculation amount, which can meet the requirement of real-time and accuracy by regulating detecting sample interval without needing of synchronous phase clocking.
出处 《现代电力》 北大核心 2016年第3期76-81,共6页 Modern Electric Power
关键词 电压暂降 变步长差分 αβ-dq变换 频率偏移 voltage sag variable step difference αβ- dqtransform frequency offset
  • 相关文献

参考文献7

二级参考文献29

共引文献211

同被引文献8

引证文献1

二级引证文献15

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部