HVDC换流站闭锁事故分析及改进措施 被引量:4

Analysis of a HVDC Converter Station Forced Blocking Accident and Improvement Measures
下载PDF
导出
摘要 某高压直流输电(HVDC)换流站发生闭锁事故,事故是由于阀冷系统循环水泵变频器不具备高低电压穿越能力造成的。根据循环水泵的启动运行方式及变频器AC/DC/AC的特性,从变频器的直流环节入手,提出基于直流支撑技术的低电压穿越改进技术,通过直流支撑系统和变频器直流环节的改造还可以实现变频器的高电压穿越。 The causes of a HVDC converter station forced blocking accident are found out,which are the frequency converter of water circulating pump in valve cooling system without the capability of high and low voltage ride through capabilities. According to the starting and operation modes of water circulating pumps and AC/DC/AC characteristics of frequency converter,measures to improve the low voltage ride through capability of frequency converter based on DC support technology is put forward.Meanwhile,high voltage ride through capability could be achieved by the reconstruction of the DC support system and the DC link of frequency converter.
出处 《供用电》 2016年第3期25-28,33,共5页 Distribution & Utilization
关键词 换流站 闭锁 变频器 直流支撑技术 高电压穿越 低电压穿越 converter station blocking frequency converter DC support technology high voltage ride through low voltage ride through
  • 相关文献

参考文献4

二级参考文献18

  • 1李强,高海容.机械密封的密封失效原因分析[J].煤矿机械,2006,27(4):685-686. 被引量:8
  • 2任达勇,邓本飞,郑丰,等.天生桥换流站运行规程[Z].兴义:中国南方电网超高压输电公司天生桥局,2006. 被引量:2
  • 3Tian-Guang HVDC transmission project: Valve cooling system Maintenance Manual[Z]. Germany: Siemens. 1999. 被引量:1
  • 4Lips H P. Water cooling of HVEC thyristor valves[J]. IEEE Trans on PWRD, 1994,9(4) : 1830-1837. 被引量:1
  • 5广州换流站运行规程[M].广州:南方电网超高压输电公司广州局,2004. 被引量:1
  • 6肇庆换流站运行规程[M].广州:南方电网超高压输电公司广州局,2005. 被引量:1
  • 7广州换流站阀冷系统维护手册[M].德国:西门子公司.2001. 被引量:1
  • 8肇庆换流站阀冷系统维护手册[M].德国:西门子公司.2004. 被引量:1
  • 9广州换流站阀冷系统软件设计手册[M].德国:西门子公司,2001. 被引量:1
  • 10肇庆换流站阀冷系统软件设计手册[M].德国:西门子公司,2004. 被引量:1