摘要 利用计算流体动力学的方法,以连通地铁站和商业区的中庭为模型,研究了火源热释放速率对中庭火灾自然排烟策略的影响.火源热释放速率分别设为2,3,4 MW,模拟结果表明:中庭采用自然排烟策略,当室外环境温度低于5℃时,火源热释放速率由2MW增大到4MW的过程中,自然排烟策略失效;当室外环境温度高于25℃时,烟气可由中庭天窗稳定排出,且随着火源热释放速率的增大,自然排烟效果增强;随着室外温度的增加,中庭内外温差减小,火源热释放速率的变化对中庭自然排烟的影响减小. The model of an atrium,combining the subway station with commercial districts,was built and the CFD(computer fluid dynamics)technology was adopted to simulate the effects of heat release rate on the natural smoke extraction strategy when fire occurs in the atrium.The heat release rate was set to be 2,3,4 MW.The simulated results indicate that,the smoke extraction strategy fails with the increase of fire heat release rate from 2 MW to 4 MW when the outdoor temperature is lower than 5 ℃.When it exceeds 25 ℃,the smoke can be extracted and the effect is better with the increase of heat release rate.With the increase of outdoor temperature and the reduction of temperature difference between outdoor and indoor environment,the effect of heat release rate on the atrium natural smoke extraction decreases.
出处 《上海理工大学学报》 CAS 北大核心 2016年第1期19-24,共6页 Journal of University of Shanghai For Science and Technology
基金 上海市科委自然科学基金资助项目(12ZR1420900) 上海市教委科研创新项目(14ZZ134) 上海市质量监督局公益科研项目(2012-12 2012-41)
关键词 中庭 数值模拟 热释放速率 自然排烟 atrium numerical simulation heat release rate natural smoke extraction
  • 相关文献

参考文献19

  • 1National Fire Protection Association. NFPA 502, Standard for road tunnels, bridges, and other limited access highways[S]. New York: New York and New Jersey Port Authority Press, 2014. 被引量:1
  • 2中华人民共和国住房和城乡建设部.GB500162013,建筑设计防火规范[S].北京:中国计划出版社,2015. 被引量:1
  • 3中华人民共和国公安部消防局.GB50045--1995,高层民用建筑设计防火规范(2005年版)[S].北京:中国计划出版社,2005. 被引量:1
  • 4National Fire Protection Association. NFPA 92B, Guide for smoke management systems in malls, atria, and large areas[S]. New York.. New York and New Jersey port authority press, 2009. 被引量:1
  • 5Hansell G O. Design approaches for smoke control in atrium building., building research establishment report BR 258[M]. England.. IHS BRE Press, 2010. 被引量:1
  • 6Chang C H, Banks D, Meroney R N. Computational fluid dynamics simulation of the progress of fire smoke in large space building atria[J]. Tamkang Journal of Science and Engineering,2003,6 (3) .-151 - 157. 被引量:1
  • 7Yi L, Chow W K, Li Y Z, et al. A simple two-layer zone model on mechanical exhaust in an atrium[J]. Building and environment, 2005,40 (7) : 869 - 880. 被引量:1
  • 8Shi C L, Lu W Z, Chow W K, et al. An investigation on spill plume development and natural filling in large full-scale atrium under retail shop fire [ J ]. International Journal of Heat and Mass Transfer, 2007,50(3/4) ..513- 529. 被引量:1
  • 9Ji Y, Cook M J, Hanby V. CFD modelling of natural displacement ventilation in an enclosure connected to an atrium[J]. Building and Environment, 2007,42 (3) .. 1158- 1172. 被引量:1
  • 10Li S C, Chen Y, Chert X, et al. Engineering numerical simulation on the amount of make-up air for mechanical smoke exhaust in atrium [J]. ProcediaEngineering, 2011,11 .. 379 384. 被引量:1

二级参考文献49

共引文献20

同被引文献20

引证文献1

二级引证文献3

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部