期刊文献+

湿烟囱GD-APC杂化聚合结构防腐层脱落失效分析 被引量:2

Failure analysis of GD- APC hybrid polymeric corrosion-resistant coating in wet stack
下载PDF
导出
摘要 贵州某电厂2×600 MW超临界机组运行1年后烟囱GD-APC防腐层出现脱落,对防腐层碎片进行了宏观分析、能谱分析及扫描电子显微镜分析,确认防腐层脱落的主要原因是施工时未严格按工艺进行控制以及运行过程中烟气温度突变,最后给出了设计、施工及运行阶段的建议。 The GD- APC hybrid polymeric corrosion resistance coatings drop off after one year operation in the stack of 2 × 600 MW hypercritical coal power units in a power plant of Guizhou province. The coating chips are analyzed through macro-structuremicroscope,energy spectrum analysis microscope and scanning electron microscope. The main reasons are that the fume-gas temperature changes abruptly and the construction is not strictly under the control of the construction procedures. At last,advice is give about the design,construction and operation stage.
出处 《华电技术》 CAS 2015年第9期65-67,共3页 HUADIAN TECHNOLOGY
关键词 湿烟囱 湿法脱硫 GD-APC防腐涂层 失效分析 wet stack GD-APC corrosion-resistant coating failure analysis