期刊文献+

特高压直流输电工程500kV GIS现场绝缘诊断及故障分析 被引量:4

On-site Insulation Diagnosis and Fault Analysis of 500 kV GIS in UHVDC Transmission Project
下载PDF
导出
摘要 以±800 kV特高压直流输电工程配套500 kV GIS的现场绝缘试验为研究对象,详细阐述了GIS现场交流耐压试验方法,并对耐压试验后SF6气体分解产物测试和投运后超声波带电局放试验进行了简要介绍,分析了试验中出现的两次绝缘击穿故障,最后对试验中相关注意问题进行了分析和阐述。 This paper takes on-site insulation test of 500kV GIS in ±800kV UHVDC transmission project as study? subject, ex-plains the method of the on-site AC withstand voltage test, has a brief introduction to the test of SF6 decomposition products after the AC withstand voltage test and the ultrasonic partial discharge test when the GIS put into operation, and analyzes the twice break-down failure during the test, finally analyzes the relevant points for attention during the test.
出处 《云南电力技术》 2015年第2期109-111,121,共4页 Yunnan Electric Power
关键词 交流耐压 局部放电 绝缘诊断 故障分析 GIS GIS AC withstand voltage partial discharge insulation diagnosis fault analysis