北方地区多联式空调机组IPLV(C)试验研究

Experimental Study on IPLV(C) of VRF Air-Conditioning System in North China
下载PDF
导出
摘要 以一拖四多联式空调系统为例,通过空调系统焓差试验性能测试,将空调系统末端各负荷比例分别调整为100%、(75±10)%、(50±10)%和(25±10)%四种情况,控制机组室外机的变频压缩机及定频压缩机启停,调节变频压缩机的工作频率、风扇电机的转动速度,测定分析多联式空调系统最佳的EER值,获得理想的制冷性能系数IPLV(C)值为4.160 3,为后续的变更程序设计思想和参数设定提供了试验依据。试验过程中,尽管有个别数据偏差较大,但从数据变化曲线上看,基本上可以反映出系统的运行规律。 With the multi-split air-conditioning system as an example, through the enthalpy differ-ence test on performance, the load proportion on air-conditioning system ends can be adjusted to four cas-es, including 100%, (75±10)%, (50±10)% and (25±10)%, in order to start and stop the inverter compressorand fixed frequency compressor of outdoor unit, regulate the working frequency of inverter compressor and the rotation speed of the fan motor, test out and analyze the optimal EER value about VRF air-conditioning system, obtain the ideal IPLV(C) value 4.160 3, provide experimental basis for the change program design and parameter setting of the subsequent. In the test process, data curve can basically reflect the operation rules of the system although there are some exceptional data with large deviation.
作者 狄春红
出处 《建筑节能》 CAS 2015年第5期13-18,共6页 BUILDING ENERGY EFFICIENCY
关键词 多联机 调节负荷 制冷综合性能系数 multi-split adjusted load IPLV(C)(Integrated Part Load Value for cooling)
  • 相关文献

参考文献8

二级参考文献68

  • 1姚冰花.基于PROFIBUS-DP总线的Danfoss变频器应用[J].微计算机信息,2005,21(2):78-79. 被引量:11
  • 2Bivens D B , et al. Performance of R32/R125/R134a mixtures in systems with accumulators or flooded evaporators.ASHRAE Transaction, 1997( I ) : 777 - 780. 被引量:1
  • 3Hwang, Y, et al. Experiences with refrigerant mixtures.ASHRAE Transaction, 1997( I ) :765 - 776. 被引量:1
  • 4Cavallini, A , et al.Working fluids for mechanical refrigelation--invited paper presented at the 19th international congress of refrigeration,the Hague,August 1995.International Journal of Refrigeration. 1996(8), VOL. 19:485 - 496. 被引量:1
  • 5Aprea, C , et al. An experimental evaluation of the greenhouse effect in R- 22 substitution.Energy Conversion and Management, 1998(9), VOL.39:877 - 887. 被引量:1
  • 6Chin,L ,et al.Issues relating to the adoption of R-410A in air conditioning systems. Proceedings of the 20th International Congress of Refrigeration,Sydney ,1999, Vol. 2: (paper 179 ). 被引量:1
  • 7Piao, C C ,et al.A study of thermodynamic properties of HFC-32/125/134a ternary mixture.Proceedings of the 19th Intemational Congress of Refrigeration,The Hague,1995,Vol.4a: 488 - 495. 被引量:1
  • 8Heide, R. The staface tension of HFC refrigerants and mixtures. International Journal of Refrigeration, 1997(7), Vol.20:496 - 5O3. 被引量:1
  • 9Klein, S A , et al.Refrigeration syslem performance using Liquid- suction heat exchangers. International Journal of Refrigeration, 2000(8 ), Vol. 23,588 - 596. 被引量:1
  • 10Mei, V C, et al. Performance tests of R - 22 and R - 32/R -125/R- 134a mixture for baseline air conditioning and liquid over-feeding operations .ASHRAE Transaction,1995( II ):1072 - 1076. 被引量:1

共引文献87

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部