针对以往火力发电厂与变电站的电气照明设计过程中,单纯依赖设计经验或手工粗略计算导致照明指标少、效果差、精度低的问题,以某火力发电厂主控室为例,介绍了运用DIALux软件建立三维仿真模型,进行多种照明方案仿真分析,优化照明设计的方法,并且通过比较实测值与仿真值的方法对软件的计算精度进行了验证。研究结果表明:DIALux软件简单易用,建模符合真实场景,具有较高的计算精度,可快速准确地计算各项照明指标及帮助设计人员提高工作效率。
The original electrical illuminance design of fossil fuel power plants and substations relies solely on design experience or hand rough calculation,which lead to the problems including less lighting index,poor effect and low accuracy. Aiming at the problem,this paper,taking a certain power plant main control room as an example,introduces the application of DIALux in the establishment of a three- dimensional simulation model,analyzes variable illuminance plans,optimizes design methods and verifies the calculation accuracy of the software by comparing measured value and simulation value. The research results show that: the DIALux,which is easy to apply,accords with the real scene modeling,enjoys high calculation accuracy,and quickly and accurately calculates the illuminance index,which helps the designers to improve the efficiency of lighting design.
出处
《黑龙江电力》
CAS
2015年第2期163-167,共5页
Heilongjiang Electric Power
关键词
DIALUX
照度计算
照度优化
仿真验证
DIAlux
illuminance calculation
illuminance optimization
simulation