摘要 分析合山电厂2号发电机并网过程零功率切机保护动作,导致并网失败的原因。通过分析故障过程的零功率切机保护录波图,并将计算所得的并网时的同期角和发电机电流值与规程值相比,得出零功率切机保护动作的原因是DEH未投入自动同步。在安装了零功率切机保护的发电机并网时,汽轮机DEH未投入自动同步会造成零功率切机保护动作切机。提出的修改运行操作票和控制逻辑的防范措施,可确保机组并网过程中DEH自动同步的投入。 The action of zero-power tripping protection of No.2 generator during the grid connection process which resulted in the grid connection failure in Heshan power plant is analyzed.By analyzing the recording graph of the zero-power tripping protection during the fault process and comparing the synchronous angle during the grid connection by calculation and the generator current value with guide values,it is obtained that the reason of the action of zero-power tripping protection is that DEH is not put into automatic synchronization.During the grid connection of generator which installs zero-power tripping protection,the zero-power tripping protection will act if the DEH of steam turbine is not put into automatic synchronization.Countermeasures of modifying the operation order and control logic are proposed,which can ensure the operation of DEH automatic synchronization during the grid connection of generator.
作者 姜金德
出处 《广西电力》 2015年第1期72-73,共2页 Guangxi Electric Power
关键词 发电机并网 DEH 自动同步 零功率切机保护 generator grid connection DEH automatic synchronizing zero-power tripping protection of generator
  • 相关文献

参考文献4

  • 1南京南瑞继保电气有限公司.RCS-985UP机组功率突降切机装置技术说明书(ZL-YJBH2010.0907) [Z].江苏:南京南瑞继保电气有限公司,2011. 被引量:1
  • 2中国大唐集团公司.关于防止汽轮机损坏的反事故措施的实施意见[Z].北京:中国大唐集团公司,2011. 被引量:1
  • 3大唐桂冠合山发电公司.670MW机组运行操作规程[Z].合山:大唐桂冠合山发电公司,2012. 被引量:1
  • 4上海新华控制技术 (集团) 有限公司..电站汽轮机数字式电液控制系统——DEH[M],2005.

同被引文献2

引证文献1

二级引证文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部