期刊文献+

碳纤维复合芯导线与钢芯铝绞线的起晕特性对比试验 被引量:7

Contrastive Study on Corona Characteristics of Aluminum Conductor Composite Core and Aluminum Conductor Steel Reinforced
下载PDF
导出
摘要 为研究碳纤维复合芯导线(ACCC)的起晕特性,基于小电晕笼电晕测量系统进行了ACCC-600/71单根导线和LGJ-630/45钢芯铝绞线单根导线起始电晕特性的对比试验。试验结果表明:在干净及人工涂污下,ACCC-600/71导线的起晕电压均要高出LGJ-630/45导线起晕电压,说明ACCC-600/71导线确实能够降低线路损耗,在节能、环保方面具有良好运行性能;表面污秽会降低导线表面粗糙度系数,从而大幅度降低起晕电压,且污秽物颗粒度越大影响程度越高。 In order to study the corona characteristics of aluminum conductor composite core (ACCC), corona onset tests of single ACCC- 600/71 conductor and I,GJ-630/45 conductor were performed based on the corona measurement system with small corona cage. The experimental result shows that: under clean and artificial smear conditions, the corona onset voltages of ACCC-600/71 conductors are higher than those of LGJ-630/45 conductor, which proves that ACCC-600/71 conductors can reduce the line losses and have good performance in energy saving and environmental protection. Surface contamination reduces the roughness factor of ACCC-600/71 and LGJ-630/45 conductors and greatly lowers the corona onset voltages. The bigger the particle size is, the higher the influence will be.
出处 《中国电力》 CSCD 北大核心 2015年第1期76-80,共5页 Electric Power
基金 国家重点基础研究发展计划(973计划)资助项目(2011CB209401) 中央高校基本科研业务费专项资金资助项目(2014 MS92)~~
关键词 碳纤维复合芯导线 钢芯铝绞线 起晕特性 电晕笼 起始电晕电压 表面粗糙系数 污秽 aluminum conductor composite core (ACCC) aluminum conductor steel reinforced (ACSR) corona characteristics coronacage corona onset voltage roughness factor contamination