摘要
对非晶合金变压器的抗短路性能进行了分析。选取1台SBH15-M-200/10非晶合金变压器进行了突发短路试验研究,研究表明,非晶合金变压器的短路冲击具有累积效应,累积4次的变形情况可能超过国家标准,需引起注意。
Short circuit resistance of amorphous alloy ransformer are analyzed. Sudden short circuit is tested and studied on a SBH15- M-200/10 amorphous alloy transformer. Research shows amorphous alloy transformer shock has a cumulative effect. The four-times cumulative deformations are likely to overrun national standard, which should be noted.
出处
《东北电力技术》
2014年第12期54-56,共3页
Northeast Electric Power Technology
关键词
变压器
非晶合金
抗短路
Transformer
Amorphous? alloy
Short circuit