摘要 燃气属于易燃易爆的危险性气体,当在室内有限空间发生泄漏时,会带来相当严重的后果。针对燃气泄漏扩散的特点,利用Gambit建立室内燃气灶喷嘴处气体泄漏扩散的物理模型,并结合CFD流体动力学软件FLUENT模拟了燃气连续泄漏的扩散过程。对燃气在一定温度梯度、不同湿度条件下的扩散效果进行了对比,并监测了指定安装区域内不同安装点处的浓度,以期达到优化报警器安装位置的目的。结果表明,室内空气的相对湿度和安装位置是影响报警时间的关键因素;在相同安装点,当空气相对湿度增加15%时,报警时间延迟近6s;在一定的空气相对湿度下,报警器距离泄漏口水平位置增加1m,报警时间滞后4s。 Gas belongs to flammable and explosive hazardous gas.When the leakage of gas occurred in limited indoor space, the serious consequences would be produced.According to the characteristics of the gas leakage diffusion,firstly Gambit was established indoor gas stove nozzle dispersion physical model.Secondly CFD fluid dynamics software FLUENT was used to simulate the diffusion process of continuous leakage.Finally comparing the diffusion results under certain temperature gradient but different moisture conditions,and monitoring the specified installation area with variety of mounting points,the aim was to optimize the installation position of the alarm.The results show that the location of distance and relative humidity of indoor air were both the key factors on affecting the alarm time.For the same mounting points,relative air humidity increasing 1 5%would cause delaying the time of alarm nearly 6 s;under the same air relative humidity,each time the alarm was away from the leaking mouth increasing by 1 metre,alarm time would lag for 4 s.
出处 《辽宁石油化工大学学报》 CAS 2014年第6期42-46,共5页 Journal of Liaoning Petrochemical University
关键词 泄漏扩散 相对湿度 安装位置 燃气报警器 优化 Leakage diffusion Relative humidity Installation position Gas alarm Optimization
  • 相关文献

参考文献14

  • 1雷达..天然气输气管道泄漏事故风险分析[D].北京化工大学,2012:
  • 2Lisboa H D M,Guillot J M,Fanlo J L.Dispersion of odorous gases in the atmosphere-Part I:Modeling approaches to the phenomenon[J].Science of the Total Environment,2006(6):220-228. 被引量:1
  • 3Michal K,Ludovit J.CFD dispersion modeling for emergency preparedness[J].Journal of Loss Prevention in the Process Industries,2009(1):97-104. 被引量:1
  • 4Herdom K C.Effects of obstacle on the Spread of a heavy gas wind tunnel simulation[J].Journal of Hazardous Materials,1992,30(2):151-194. 被引量:1
  • 5Jo Y D,Ahn B J.A method of quantitative risk assessment for transmission pipeline carrying natural gas[J].Journal of Hazardous Materials,2005,23(2):1-12. 被引量:1
  • 6张甫仁,张辉,庄春龙.室内燃气泄漏浓度场变化规律研究[J].建筑科学,2010,26(2):108-113. 被引量:7
  • 7于畅,田贯三.可燃气体室内泄漏扩散的研究[J].山东建筑工程学院学报,2006,21(3):243-247. 被引量:23
  • 8中华人民共和国建设部.CJ3057—1996家用燃气报警器[S].北京:中国建筑工业出版社,1996. 被引量:1
  • 9王福军编著..计算流体动力学分析 CFD软件原理与应用[M].北京:清华大学出版社,2004:272.
  • 10罗惕乾,程兆雪,谢永耀.流体力学[M].北京:机械工业出版社.2010. 被引量:2