期刊文献+

闭式冷却水板式换热器的应用与维护 被引量:4

Application and Maintenance of Plate Heat Exchanger with Closed Cooling Water
下载PDF
导出
摘要 结合秦山第二核电厂闭式冷却水换热器选用的实例,介绍了板式换热器的结构,以及运行中因海水含泥沙量大,板片容易在海水入口和出口处发生磨损穿孔的情况。通过对发生穿孔的原因进行分析,提出了破损板片的修补方案,对板式换热器在电厂的应用和维护提出了建议。 Taking the heat exchanger applied in Qinshan Phase II Nuclear Power Plant as an example, an introduction is being presented to the structure of its plate heat exchanger, as well as to the wear failures frequently encountered at sea water inlet and outlet due to high sand content in sea water. By analyzing the wear causes, repair schemes are proposed for worn plates, and suggestions for application and maintenance of the plate heat exchanger are put forward simultaneously.
出处 《发电设备》 2014年第6期435-437,共3页 Power Equipment
关键词 核电厂 板式换热器 磨损 维护 nuclear power station plate heat exchanger wear maintenance
  • 相关文献

参考文献3

  • 1黄惠明,王义刚,蓝尹余.杭州湾悬浮泥沙浓度分布及其探讨[C]//第十四届中国海洋(岸)工程学术讨论会论文集.北京:海洋出版社,2009:736-738. 被引量:1
  • 2Neville A, McDougall B A B. Erosion and cavitation corro- sion of titanium and its alloys [J]. Wear, 2001, 250 ($1): 726-735. 被引量:1
  • 3Bermudez M D, Carrion F J, Martinez N G, et al. Erosion Corrosion of stainless steels, titanium, tantalum and zireoni um[J]. Wear, 2005, 258 (1),693-700. 被引量:1