期刊文献+

主流区理论——我国医院洁净手术室要求集中布置送风口的理论基础 被引量:19

Main flow area theory: the basis of central air supply in hospital operating rooms in China
下载PDF
导出
摘要 我国标准将洁净手术室分为四级 ,其中前三级要求在手术台上方集中布置送风口 ,这样做是为了保护关键区域 ,符合我国早就提出的局部净化和主流区理论。按主流区理论计算结果表明 ,这样布置送风口 ,将在同样换气次数下使手术台区洁净度提高一个级别 ,使主流区细菌浓度和周边区细菌浓度之比降到 0 . The operating rooms are classified by their cleanliness into four grades as stipulated in a China's national standard. It is required that a central air supply ceiling directly over the operating table for the first three grades of operating rooms. This arrangement, based on the main flow theory founded as early as later 1970s in China, can effectively protect the critical area, upgrading the space cleanliness while the air changes remain the same and keeping the ratio of criteria concentrations in the main flow area and the peripheral area under 0.5.
出处 《暖通空调》 北大核心 2001年第5期2-6,共5页 Heating Ventilating & Air Conditioning
关键词 医院 洁净 手术室 主流区 送风口 hospital, cleaning, operating room, main flow area
  • 相关文献

参考文献7

  • 1许钟麟编著..洁净室设计[M].北京:地震出版社,1994:255.
  • 2许钟麟著..空气洁净技术原理[M].上海:同济大学出版社,1998:548.
  • 3梅自力编著..医疗建筑空调设计[M].北京:中国建筑工业出版社,1991:199.
  • 4沈晋明.德国的医院标准和手术室设计[J].暖通空调,2000,30(2):33-37. 被引量:49
  • 5《空气洁净技术措施》编制组编..空气洁净技术措施[M].北京:中国建筑工业出版社,1979:78.
  • 6许钟麟.洁净室的不均匀分布计算法.建筑学会暖通空调专业委员会成立大会论文集[M].,1978.. 被引量:1
  • 7许钟麟,张益昭,张彦国,刘华,梅自力,沈晋明,郭大荣,江培成.洁净空间新型气流分布方式的机理和特性研究[J].暖通空调,2000,30(3):1-7. 被引量:4

二级参考文献18

  • 1许钟麟,张益昭.改善室内空气品质的重要手段——新风过滤处理的新概念[J].暖通空调,1997,27(1):5-9. 被引量:30
  • 21,Schramik E R. Taschenbuch für Heizung+Klima Technik, 97/98. Oldenburg Verlag Müchen, 1997. 被引量:1
  • 32,DIN 1946/4. Room Ventilation Technique, Ventilation in Hospital, 12. 1989. 被引量:1
  • 43,DIN 4799. Air Conduction Systems for Operating Room, Testing, 12.1988. 被引量:1
  • 54,Esdorn H, Nouri Z. Vergleichsuntersuchungen über Luftführungssysteme mit Mischstrmung in Operationsrumen. HLH 28, 1977(4). 被引量:1
  • 65,Galson E, Eftekher N. Hospital air conditioning and sepsis control. ASHRAE J, 1968,(7). 被引量:1
  • 76,Intage C, Wiebe H A, Partain C L. An investigation of the importance of air flow in control of postoperative infections. ASHRAE J, 1982,(2). 被引量:1
  • 87,Fitzner K. Operationsraum-Zuluftdecken. XXII. Internationaler Kongress Technische Gebudeausrüstung, Berlin, 1989. 被引量:1
  • 98,Schmidt P. OP-Zuluftdecken-Funktion, Beurteilung, Einbau, Betrieb, Kosten, TK'91 Technik im Krankenhaus “Sanierung von Krankenhusern in Ost und West”, Hannover, 10. 1997. 被引量:1
  • 109,Schmidt P. Mglichkeiten und Grenzen der Energieeinsparung bei der Klimatisierung von OP-Abteilungen., TK'92 Technik im Krankenhaus, “Durch Eigeninstandhaltung und Fremdservice zum sicheren und konomischen Krankenhausbetrieb”, Hannover, 9. 1992. 被引量:1