摘要
简单介绍了三峡左岸电站 14台发变组内部故障主保护及TA配置方案 ,对清华大学关于三峡发电机内部故障主保护及TA配置方案所做的工作进行了总结 ,从主保护配置方案的灵敏性、发电机中性点侧TA的数目等方面对两种保护方案进行了对比 ,为三峡工程今后的工作提供借鉴。
Firstly,the main protection scheme of internal fault and disposition of current transformer are simply introduced for the generator transformer in Three Gorges Left Bank Power Station.Then,the research work of Tsinghua University in these aspects in reported.Finally,two kinds of protection scheme are compared from the view of the sensitivity of the main protection scheme and the number of current transformers near neutral point of the generator.Those works can be used as reference for the future work in Three Gorges Power Station.
出处
《继电器》
CSCD
北大核心
2002年第2期29-33,50,共6页
Relay
关键词
三峡电站
发电机
故障
主保护
灵敏性
电流互感器
Three Gorges Power Station
generator
internal fault
the disposition of main protection scheme and current transformer
sensitivity