摘要 ATSC型快速动态无功补偿装置采用新颖的快速无功功率检测方法和独特的晶闸管控制技术 ,通过微机实现了对多组电容器快速自动分级投切 ,达到了对冲击负荷动态无功补偿的要求 ,其在工频 50 Hz情况下的全部响应时间小于 1 6ms。文中介绍了该装置主回路控制方式和控制电路构成 ,通过其型式试验检测报告中的有关数据和波形及用户现场实测波形 ,表明该装置已达到技术性能指标 ;并简要介绍了现场运行效果。 A rapid reactive power detecting method with a special thyristor controlling is proposed and used in a new fast dynamic reactive power compensation device, which is able to switch capacitors rapidly without any impact, and response time of which is less than 16 ms under the 50 Hz frequency. The control mode of the main circuit and the schematic block of the device are also presented in detail. The relevant data and waveforms from test and the actual consumer report show that the device is effective. This project is supported by Doctoral Fund, Ministry of Education, China (No. 1999007904).
出处 《电力系统自动化》 EI CSCD 北大核心 2001年第10期51-54,共4页 Automation of Electric Power Systems
基金 国家教育部博士学科点专项科研基金资助项目!(19990 0 790 4)
关键词 晶闸管控制 电力系统 动态无功补偿装置 ATSC型 交流接触器 Capacitors Dynamic response Switching systems Thyristors Waveform analysis
  • 相关文献

参考文献10

  • 1王兆安等编著..谐波抑制和无功功率补偿[M].北京:机械工业出版社,1998:364.
  • 2孙涵芳..INTEL 16位单片机[M],1995.
  • 3苏文成,金子康等编著..无功补偿与电力电子技术[M].北京:机械工业出版社,1989:160.
  • 4陈允平,刘会金,彭辉,付立军,陈琼琼.微机控制的晶闸管开关型低压配电网基波无功分相补偿[J].电网技术,1999,23(4):57-61. 被引量:15
  • 5李鹏.电弧炉用TCR微机控制调节器装置的研制(硕士学位论文)[M].保定:华北电力大学,1993.. 被引量:1
  • 6王兆安,谐波抑制和无功功率补偿,1998年 被引量:1
  • 7孙涵芳,Intel 16位单片机,1995年 被引量:1
  • 8李鹏,硕士论文,1993年 被引量:1
  • 9Lin C E,IEEE Trans Power Systems,1989年,4卷,2期,643页 被引量:1
  • 10苏文成,无功补偿与电力电子技术,1989年 被引量:1

二级参考文献3

共引文献14

同被引文献78

引证文献15

二级引证文献124

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部