研究了大温差空调水系统供回水温差和空气处理过程、末端、水泵和输送管道、主机四个方面之间的关系,结果表明:空调冷水系统大温差不宜超过9℃。分析了采用大温差空调水系统的设计要点,并提出了针对大温差空调水系统的一些优化设计方法。
The paper discusses the relationship between the supply-return water temperature difference of chilled water system with large temperature difference&air condition process, terminals, water pumps&pipes water cool chillers, the result shows:the temperature difference of chilled water system with large temperature difference should not exceed 9℃;analyzes the key design elements of chilled water system with large temperature difference adopted in projects; and offers a series of optimum design methods of chilled water system with large temperature difference.
出处
《制冷与空调(四川)》
2014年第3期321-326,共6页
Refrigeration and Air Conditioning
关键词
大温差
空调水系统
设计方法
large temperature difference
water system of air-condition
design method