摘要 设备和管道系统的承压能力是影响空调水系统竖向分区的主要因素。通过对国内外30余项规范标准及10多个厂商产品参数的调研,分析了空调系统主要设备、管道及连接方式的承压能力;结合20个工程案例,对国内外在建和建成的典型超高层建筑空调水系统形式和竖向分区方法进行了归类总结;基于理论与工程案例分析,得出了超高层建筑空调水系统竖向分区原则和不同高度超高层建筑水系统竖向分区方案。 The pressure bearing capacity of equipment and pipeline system is a main factor affecting vertical zoning of air conditioning water system. Based on the research of more than thirty standards at home and abroad, as well as parameters of various products from more than ten manufacturers, analyses the pressure bearing capacity of major equipments, pipes and connections of air conditioning systems. Combined with twenty projects, classifies and summarizes the forms of air conditioning water system and the methods of vertical zoning in typical super high-rise buildings in the construction and completion at home and abroad. According to analysis in theory and by project cases, obtains both the principles and the schemes of vertical zoning of air conditioning water system in super high-rise buildings with different heights.
作者 张铁辉 赵伟
出处 《暖通空调》 北大核心 2014年第5期2-9,共8页 Heating Ventilating & Air Conditioning
关键词 超高层建筑 空调水系统 竖向分区 管道承压设备承压 super high-rise building, air conditioning water system, vertical zoning, pressure bearingof pipeline, pressure bearing of equipment