期刊文献+

变风量空调系统风量平衡调试方法浅析 被引量:8

Asimpleanalysis on the Air Volume Balance Commissioning Method for VAV Air Conditioning System
下载PDF
导出
摘要 以实际工程为背景,分析了目前变风量空调系统末端风量平衡调试的基本原理及存在的问题。基于对现有变风量空调系统末端装置的风量平衡调试方法的不足提出了相应的解决的方法:动态风量平衡与静态风量平衡相结合。这种调试方法在实际工程的调节中得到良好的验证,可保证调试后的变风量空调系统运行满足房间舒适度以及较好地发挥变风量空调系统的节能作用。为建立适用于我国变风量空调系统风量平衡的标准调试方法提供了借鉴。 Based on a practical project, thispaper analyzedthebasic principle and limitation of current air volume balance debugging method for the terminal of the variable air volume (VAV) air conditioning system. We also proposed a solution to improve the currentmethod: combined dynamic air volume balance with static air volume balance. The improved method was verifiedin a practical project. The VAV air conditioning system,which was debugged by this improved method, meets the requirement of room comfort and adequatelysaves the consumption of energy. Thus the improved method would provide a reference for the establishmentof a suitable national standard of air volume debugging method forVAV air conditioning system.
出处 《洁净与空调技术》 2014年第1期20-23,共4页 Contamination Control & Air-Conditioning Technology
关键词 风量平衡 动态平衡 静态平衡 变风量空调 Air volume balance Dynamic balance Hydrostatic equilibrium VAV air conditioning system
  • 相关文献

参考文献9

二级参考文献9

共引文献12

同被引文献25

引证文献8

二级引证文献16

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部