期刊文献+

低频叠加法电源参数的优化及影响

Optimization and Effect of Low- frequency Superposition Method on Power Parameters
原文传递
导出
摘要 针对XLPE电缆绝缘监测中低频叠加法电源参数对检测精度的影响问题,研究了XLPE电缆绝缘故障检测精度、选择性与低频叠加电源参数之间的关系,综合考虑低频叠加法电源幅值和频率2个因素进行实验分析。结果表明,在一定频率下,随着叠加电源幅值的降低,阻性电流成分增大,绝缘检测精度相应提高;在一定电压下,随着叠加电源频率的降低,电缆绝缘检测精度逐渐升高,低频叠加法对电缆故障的选择性越好。 In order to solve problems that power parameters of low - frequency superposition method have an effect on detection accuracy of insulation resistance in XLPE cable insulation detection, it deeply studied the relationship between the power parameters of low - fre- quency superposition and detection accuracy or fault selection of XLPE cable insulation. Then it did the experiment and simulation con- sidering the amplitude and frequency of power. The results showed that resistance current components and detection accuracy would be gradually increased with the reduction of power amplitude at a certain frequency; under a certain voltage, detection accuracy of cable insulation was increased and the frequency superposition method had a better fault selectivity while the power frequency decreased.
出处 《煤矿安全》 CAS 北大核心 2014年第1期95-97,共3页 Safety in Coal Mines
基金 国家高技术研究发展计划(863计划)资助项目(2012AA06A405) 山西省科技重大专项资助项目(20111101024)
关键词 低频电源 XLPE电缆 绝缘监测 阻性电流 检测精度 low - frequency power XLPE cable insulation monitoring resistive current detection accuracy
  • 相关文献

参考文献8

二级参考文献17

  • 1彭建飞,任岷,王树锦.MATLAB在电力系统仿真研究中的应用[J].计算机仿真,2005,22(6):193-196. 被引量:27
  • 2蔡国雄,胡兆明,王建民.介质损耗测量的过零点电压比较法[J].电网技术,1995,19(10):1-5. 被引量:35
  • 3郑晓泉,曹晓珑.XLPE电缆护套电阻及接地化学电势对在线诊断的影响及其测量方法[J].电线电缆,1996(4):20-22. 被引量:10
  • 4H. Muto et al. Development of New Diagnostic Method for Hot-Line XLPE Cables With Water Trees[J]. IEEE Trans. on Power Delivery, Vol. PWRD-2, No. 1,1987. 被引量:1
  • 5A. Nakajima. Development of a Hot-line Diagnostic Method for XLPE Cables and the Measurement Results[J]. IEEE Trans.on Power Delivery, 1989,4 (2). 被引量:1
  • 6S. Yamaguchi. Development of a New Type Insulation Diagnostic Method for Hot-line XLPE Cables[J]. IEEE Trans.on Power Delivery, 1989,4 (3). 被引量:1
  • 7S. Yamagcuchi. Improvent of the XLPE-Insulated Distribution Cables and Development of the Hot Line Cable Monitoring Systems [C]. 10th International Conference on Electricity Distribution, 1989. 被引量:1
  • 8TaKao Kumazawa. A New Hot-line Diagnostie Method for XLPE Power Cables-AC Superpwsition Method [C].Proceedings of the 5th International Conferenee on Properties and Applieations of Dieleetrie Materials. 1997. 被引量:1
  • 9Yukihiro Yagi. Study on Diagnostic Method for Water Treed XLPE Cable by loss Current Measurement[C]. Annual Report Conference on Electrical Insulation and Dielectric Phenomena.1998. 被引量:1
  • 10Kumazawa T, Hotta M, Sugiyama S. et al, A new hot-line diagnostic method for XLPE power cables-AC superposition method[C]. Proceedings of the 5th International Conference on Properties and applications of Dielectric Materials. Seoul, Korea, 1997: 394-397. 被引量:1