期刊文献+

超特高压同塔4回输电线路工频电场强度的计算

Calculation of Electric Fields of EHV/UHV Transmission Lines with Four Circuits on the Same Tower
下载PDF
导出
摘要 通过对输电线路适当等效建模,应用模拟电荷法在输电线内部设置模拟线电荷,计算了超特高压同塔4回线路的导线表面电场强度和距地面1.5m处的工频电场强度,并与目前的特高压双回鼓型塔、单回猫头塔、单回酒杯塔和单回紧凑塔进行比较。结果表明,同塔4回线路的导线表面电场强度不高于其他塔型,同时地面工频电场强度要明显小于其他塔型。其理论依据为同塔的500kV导线屏蔽了1 000kV导线在地面方向的大部分电场。 After modeling a transmission line with double 1 000 kV circuits and double 500 kV circuits on the same tower, electric field intensity on the wire surface of the 4 EHV/UHV circuits and the filed at 1.5 m above ground are calculated. By setting charges in the transmission lines with a charge simulation method, the current UHV double circuits drum power, single circuit cat head tower, single circuit glass tower, and single circuit compact tower are compared with this four circuit transmission lines. The results show that the electric field intensity on the transmis sion line surface of the circuits is no higher than the other towers. Meanwhile, the power frequen cy electric field intensity on the ground is clearly less than the other towers. The theoretical basis is that 500 kV wires on the same tower shield the majority of electric field in the ground direction of the 1 000 kV wires.
出处 《上海电机学院学报》 2013年第5期268-271,291,共5页 Journal of Shanghai Dianji University
基金 黑龙江省自然科学基金项目资助(QC2012C055) 中央高校基金项目资助(DL12BB02) 东北林业大学大学生科研训练项目资助(2012068)
关键词 特高压 同塔四回 电场强度 模拟电荷法 ultra-high voltage four circuits on the same tower electric field intensity charge simulation method
  • 相关文献

参考文献12

二级参考文献106

共引文献286

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部