期刊文献+

一种智能变电站典型设计方案中的保护死区研究 被引量:4

Research of Protection Dead Zone in the Typical Design of a Kind of Smart Substation
下载PDF
导出
摘要 针对《国家电网公司输变电工程通用设计-110(66)~750 kV智能变电站部分(2011年版)》的D-3设计方案,讨论了其中500 kV部分主接线的CT(电流互感器)配置方案造成边开关和中开关存在断路器失灵死区的问题,分析了不同准确级电流互感器的特性,提出了两种可行的解决方案,为后续智能站设计避免此类问题提供依据。 In this paper, based on the design of D-3 regulated in Power Transmission and Transformation Project General Design about -110 (66) - 750 kV Smart Substation issued by State Grid Corporation (2011), the protection dead zone existing in the side switch and the middle switch which is caused by CT configuration of 500 kV main connection scheme is discussed. Then the characteristics of current transformers between different accuracy classes are analysed, and two feasible solutions are provided for the design of smart substations to avoid the same problems in the future.
出处 《山西电力》 2013年第3期1-3,共3页 Shanxi Electric Power
关键词 智能变电站 典型设计 电流互感器 保护死区 smart substation typical design current transformer protection dead zone
  • 相关文献

参考文献7

  • 1冯军主编..智能变电站原理及测试技术[M].北京:中国电力出版社,2011:293.
  • 2国家电网公司智能电网部.Q/GDW383--2009智能变电站技术导则[s].北京:中国电力出版社,2010. 被引量:1
  • 3国家电力调度通信中心.Q/GDW441--2010智能变电站继电保护技术规范[s].北京:中国电力出版社,2010. 被引量:1
  • 4刘振亚主编..国家电网公司输变电工程通用设计 110(66)-750KV智能变电站部分 2011年版[M].北京:中国电力出版社,2011:149.
  • 5中国电机工程学会继电保护专业委员会.GB T14285--2006继电保护和安全自动装置技术规程[s].北京:中国电力出版社,2006. 被引量:1
  • 6中国电力企业联合会.DL/T866--2004电流互感器和电压互感器选择及计算导则[s].北京:中国电力出版社,2004. 被引量:1
  • 7于伟城,白瑞,郝伟.智能变电站二次设备检修处理机制分析探讨[J].山西电力,2012(5):21-23. 被引量:15