摘要
通过实际案例分析了空调机组冷却水泵星三角起动时断路器跳闸故障原因,提供了两种解决方法。明确了星三角、软起动器、变频器3种方式的适用场合。指出目前空调水系统中大功率水泵更适用软起动器。
This paper analyzed the circuit breaker trip fault reasons whan star-delta pump starting and gave two methods to solve the problem. Making clear the applicability of three pump starting mode (Varied Speed Drive, VSD), soft start and star-delta starting mode. And the paper pointed out that soft start is better for big power water pump in air-conditioning system.
出处
《低压电器》
2013年第7期50-52,共3页
Low Voltage Apparatus
关键词
断路器
跳闸
力矩
堵转
冲击电流
星三角转换
带载起动
circuit breaker trip
torque
stalling
impact current
star-delta transfer
load-starting