摘要
介绍了精确下送风空调系统的原理和系统组成,并对某采用精确下送风空调系统的通信机房的能源利用效率进行测试分析,实测结果表明:该通信机房的能源利用效率达到1.54,比某大型通信集团广东公司通信机楼的平均值优23.0%,节能效果明显。
The principle and system components of the accurate downside air supply air-conditioning system was described. And the power usage effectiveness of the communication room equiped with the accurate downside air supply air-condi- tioning system was tested and analyzed. The results showed that: The power usage effectiveness of the communication room reached 1.54, than the average power usage effectiveness of a large communications group Guangdong company communication buliding excellent 23.0%, the energy-saving effect of the communication room was obvious.
出处
《洁净与空调技术》
2013年第1期80-82,共3页
Contamination Control & Air-Conditioning Technology
关键词
通信机房
精确下送风空调系统
架空地板
能源利用效率
Communication room
Accurate downside air supply air-conditioning system
Raised floor
Power usage effec-tiveness