期刊文献+

主动移频孤岛检测参数对并网电能品质的影响 被引量:2

Influence of Active Frequency Drift Islanding Detection Parameters on Power Quality on Grid
下载PDF
导出
摘要 采用Qf0×Cnorm空间描述法分析主动移频式孤岛检测方法的检测盲区,对带正反馈的主动移频式(AFDPF)孤岛检测方法的盲区大小与反馈增益间的关系进行了分析,并对初始扰动系数进行了修正,减小AFDPF孤岛检测法对并网电能品质的影响。运用Matlab软件分析比较了修正前后的孤岛检测盲区。仿真结果表明,参数修正后孤岛检测盲区明显把盲区推向更高品质因数区域,而且降低了谐波畸变率。实现了品质因数小于2.5时,AFDPF孤岛检测方法存在无孤岛检测盲区区域。 Non-detection zones (NDZs) are important index to evaluate the performance of islanding detection methods. A proper NDZs mapping can reflect application area of islanding detection effectively. In this paper,Qf0×Cnorm, space mapping is adopted in NDZs detection of active frequency drift with positive feedback (AFDPF). Relationship between NDZs size of AFDPF and feedback gain is deduced, and coefficient of initial disturbance is amended. NDZs are compared by simulation before and after coefficients are amended. Simulation results reveal that NDZs after coefficient amended are located in high factor of quality area and the harmonic distortion is reduced, if factor of quality is less than 2.5, there are no NDZs for AFDPF of islanding detection.
出处 《机械制造与自动化》 2013年第1期184-186,共3页 Machine Building & Automation
关键词 正反馈主动移频 孤岛检测 检测盲区 谐波畸变率 active frequency drift with positive feedback(AFDPF) islanding detection non-detection zones(NDZs) harmonic distortion
  • 相关文献

参考文献10

  • 1杨以涵,张东英,马骞,刘文颖.大电网安全防御体系的基础研究[J].电网技术,2004,28(9):23-27. 被引量:63
  • 2印永华,郭剑波,赵建军,卜广全.美加“8.14”大停电事故初步分析以及应吸取的教训[J].电网技术,2003,27(10):8-11. 被引量:462
  • 3IEEE Recommended Practicefor Utility Interface of Photovoltaic Systems[ S]. IEEE Standard 929-2000,2000. 被引量:1
  • 4吕振,杨丽.并网光伏发电系统的孤岛检测[J].中国电力,2009,42(3):71-74. 被引量:10
  • 5刘芙蓉,康勇,段善旭,王辉,王志峰.一种有效的孤岛检测盲区描述方法[J].电工技术学报,2007,22(10):167-172. 被引量:40
  • 6杨海柱..小功率光伏并网发电系统最大功率跟踪与孤岛问题的研究[D].北京交通大学,2005:
  • 7Ishida T, Yugo M, Makno Y. Anti-islanding protection using a twin-peak band-pass filter in interconnected PV systems and sub- stantiating evaluations [ C ]. Proc. of 1 st World Conference on Photovoltaic Energy Conversion, 1994 : 1077-1080. 被引量:1
  • 8Lopes L, Sun H, Performance assessment of active frequency drif- ting islanding detection methods [ J ]. IEEE Transactions on Energy Conversion, March 2006 : 171-180. 被引量:1
  • 9Ropp M, Rohatgi M. Determining the relative effectiveness of is- landing detection methods using phase criteria and nondetection zones [ J]. IEEE Transaction on Energy Conversion ,2000,15: 290-296. 被引量:1
  • 10Y. Jung, J. Choi, B. Yu, G. Yu, J. So, J. Choi. A Novel Active Frequency Drift Method of Islanding Prevention for the grid-con- nected Photovoltaic Inverter[ J]. IEEE Trans in Power Deliver, 2005 : 1915-1921. 被引量:1