电容式电压互感器二次电压异常分析处理 被引量:31

Analysis and Treatment on Abnormal Secondary Voltage of Capacitor Voltage Transformers
下载PDF
导出
摘要 介绍了刚投运3个月的500 kV电容式电压互感器二次电压出现异常时的处理方法,分析得出了二次电压异常的原因是由于CVT内部均压电容击穿,通过对CVT进行试验和解体检查,证明了原材料的选用和制造工艺是造成均压电容击穿的主要原因。最后对500 kV电容式电压互感器的运行维护和产品生产提出了建议。 In this article, the treatment method in case of abnormal secondary voltage of 500 kV ca- pacitor voltage transformers which just puts into operation for three months is introduced; the abnor- mal secondary voltage is due to the breakdown of internal grading capacitance in the CVT. Through test of CVT and disassembly inspection, it is proved that the main cause of grading capacitance breakdown is the selection of raw material and manufacturing process. Finally, the suggestions for operation, maintenance and production of 500 kV capacitor voltage transformers have been pro- posed.
出处 《电力电容器与无功补偿》 2012年第3期73-76,共4页 Power Capacitor & Reactive Power Compensation
关键词 电容式电压互感器(CVT) 介损 电容器 击穿 capacitor voltage transformer (CVT) dielectric loss capacitors breakdown
  • 相关文献

参考文献13

二级参考文献44

共引文献146

同被引文献207

引证文献31

二级引证文献146

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部