期刊文献+

600MW超临界直接空冷机组空冷系统防冻技术改造 被引量:1

Antifreezing Technology Conversion to Air Cooled System of 600 MW Supercritical Direct Air Cooled Units
下载PDF
导出
摘要 针对极寒地区超临界直接空冷机组冬季易冻结问题,国华呼伦贝尔电厂在机组建设阶段进行了主汽疏水及在第2、6逆流段增设真空系统温度测点及在蒸汽蝶阀后增设温度测点的技术改造。改造后经过-47℃环境温度下运行与-30℃环境温度下启、停检验,未发生冻结现象,防冻效果良好,为极寒地区超临界直接空冷机组防冻提供了借鉴。 Supercritical direct air cooling units for extreme cold regions in winter are easy to freeze. Technical revamp of main steam drain, adding vacuum temperature measuring point in No.2 and No.6 countercurrent segment and temperature measuring point after the addition of steam butterfly valves is carried out during unit construction phase of Guohua Hulunbeier Power Plant. After technical transformation, power units can operate in-47 ℃ ambient temperature normally, and can run start and stop in ambient temperature of-30 ℃ without any freezing phenomenon occurred. It provides successful experiences of antifreeze to supercritical direct air cooling units in extreme cold regions.
作者 耿群 王艳丽
出处 《内蒙古电力技术》 2012年第2期94-96,共3页 Inner Mongolia Electric Power
关键词 超临界直接空冷机组 极寒地区 主汽疏水 蒸汽蝶阀 温度测点 防冻 supercritical direct air cooled units extreme cold regions main steam drain steam butterfly valves temperature measuring point antifreeze
  • 相关文献

参考文献3

  • 1李新江.直接空冷系统优化专题报告[R].西安:西北电力设计院,2005:3-4. 被引量:1
  • 2杨迎哲.直接空冷系统自主化专题报告[R].西安:西北电力设计院,2005:4. 被引量:1
  • 3赵栓荣.直接空冷系统防冻专题报告[R].西安:西北电力设计院,2005:3. 被引量:1

同被引文献4

引证文献1

二级引证文献4

相关作者

内容加载中请稍等...