Method of Fault Area & Section Location for Non-solidly Earthed Distribution System 被引量:28

Method of Fault Area & Section Location for Non-solidly Earthed Distribution System
下载PDF
导出
摘要 中国中压配电网以架空线为主,多为小电流系统,单相接地故障占到电网故障总数的80%以上,但中国配网自动化系统基本上没有小电流接地故障定位功能,使配网自动化系统在提高可靠性的作用上大打折扣。给出一种小电流接地故障区段定位新方法,在线路上配置广域相量测量固定测点,获取小电流电网单相接地故障特征信息。基于测点相邻矩阵区段起始测点标识向量和故障路径标识向量概念,提出确定故障区间边界节点算法。物理模拟实验和挂网测试表明:该故障分区分段定位方法能够在线求解小电流接地故障段边界节点,缩小线路维护巡视范围。确定故障区间边界节点算法还可用于确定故障区相关负荷开关,为线路维护和馈线自动化提供依据。 Medium voltage distributions in China mainly use overhead lines; and most them are small current systems, whose single phase to-earth fault accounts for over 80% of the total failure in power grid. Fault monitoring is one of the main functions of distribution automation, so the new generation of power distribution automation systems in China should thoroughly solve the problem of the orientation of small current grounding fault.
出处 《中国电机工程学报》 EI CSCD 北大核心 2012年第13期I0014-I0014,197,共1页 Proceedings of the CSEE
基金 国家自然科学基金项目(60974125).
关键词 断层破碎带 配电自动化系统 单相接地故障 小电流系统 小电流接地 架空线路 电压分布 故障监测 distribution automation overhead line small-current-to-earth fault area & section location wide area phasormeasurement