Experimental investigation on the energy-saving diffuser of a main fan 被引量:1

Experimental investigation on the energy-saving diffuser of a main fan
下载PDF
导出
摘要 The main fan diffuser in a coal mine is an energy-recycling equipment with a dynamic energy loss for the main fan. Engineering practices and related researches show that the body structures of three types of diffusers are irrational. To solve the problem, an energy-saving diffuser is designed on the basis of the velocity potential theory. Under conditions of inlet velocity from 7 m/s to 32 m/s, 7 condition experiments using the energy-saving diffuser of 2.31 AER (area-enlarging ratio) and 5 condi- tion experiments using the energy-saving diffuser of 2.00 AER were conducted. Through a comparative analysis of the experi- ments, the results show that the COP (coefficient of performance) of the energy-saving diffuser of 2.31 AER is better than that of the energy-saving diffuser of 2.00 AER.
出处 《Journal of Coal Science & Engineering(China)》 2012年第1期108-112,共5页 煤炭学报(英文版)
关键词 energy-saving diffuser mine main fan COP (coefficient of performance) model experiment 条件实验 煤矿主扇 扩散器 节能 能量损失 回收设备 工程实践 散体结构