600MW发电机转子匝间短路故障诊断及处理 被引量:4

Diagnosis of the Turn-to-turn Short Circuit of 600 MW Generator Rotor Windings and Its Treatment
下载PDF
导出
摘要 机组大修时通过测量转子直流电阻、交流阻抗和两极电压等多种试验方法的分析,发现发电机转子绕组匝间短路。利用测量层间电压法对故障点进行准确定位,对故障点处理后,转子试验数据合格,投入正常运行,根据处理过程对今后的转子检修提出相应的预防措施。 In unit overhaul, we discovered turn-to-turn short circuit of rotor windings, after analysis of several test meth ods,such as dc resistance test, ac impedance test and measuring bipolar voltage. Then accurate positioning to fault point had been realized by measuring voltage between layers. The rotor test data met the requirements after treatment of fault point,and the generator put into normal operation. According to treatment process we put forward corresponding homologous prevention measures on rotor maintenance in the future.
出处 《山东电力技术》 2012年第1期48-51,54,共5页 Shandong Electric Power
关键词 发电机 转子 匝间短路 诊断 处理 generator rotor turn-to-turn short circuit diagnosis treatment
  • 相关文献

参考文献3

二级参考文献2

  • 1DL/T 596-1996.电力设备预防性试验规程[S].北京:中国电力出版社,1997. 被引量:1
  • 2GB 50150-1991.电气装置安装工程电气设备交接试验标准[S].北京:中国计划出版社,1999. 被引量:1