期刊文献+

架空线路故障指示器的整定原则与仿真验证 被引量:1

The Overhead lines Fault Indicator Setting Principle and Simulation Test and Verify
下载PDF
导出
摘要 通过分析上海某区域的10 kV中性点经小电阻接地系统的故障特点,制定了一套适合10 kV中性点经小电阻接地系统电网的故障指示器整定原则,并根据该整定原则对某型号的故障指示器进行实时数字仿真(RTDS)测试,验证了整定原则的正确性和精确性,并对10 kV中性点经小电阻接地系统故障指示器的选型,提供了数据及建议。 Based on the faults parameters of low-resistance grounding system in some area of Shanghai, we set out a group of settings which suits for overhead line fault circuit indicator. And we tested some types of fault circuit indicators that applied this group of settings in RTDS system. The RTDS simulation results validated the correction and precision of settings. Also in this article we gave some conclusions which may help for the choice of fault circuit indicators of low-resistance grounding system in 10 kV distribution grid.
出处 《电力与能源》 2011年第5期364-366,共3页 Power & Energy
关键词 架空线路 故障指示器 小电阻接地系统 整定 overhead line fault circuit indicator low-resistance grounding system settings