期刊文献+

惠州抽水蓄能电站球阀动水关闭试验研究 被引量:8

Test and research on spherical valve dynamic closing of Huizhou Pumped Storage Power Station
下载PDF
导出
摘要 惠州抽水蓄能电站B厂为评价球阀及相关设备的抗振性能和安全性,进行5号机组球阀动水关闭试验。结果表明,正常运行工况下引水系统满足设计要求,而在动水关球阀过程中由于水击作用,负荷越大,对应压力钢管的动力响应越大,水平动位移超过了规范允许值,应加强监测和观察。同时球阀与混凝土支墩之间存在相对移动,应长期保持球阀滑板的润滑。 The spherical valve and it's related equipment of 5th unit of Huizhon pumped storage power station was tested to evaluate it's anti-vlbrstion ability and safety during dynamic dosing. The test results show that the dynamic responses of the water tunnal meet design requirement under normal condition. The greater the loed is, the greater the dynamic response of the pipes and the concrete buttress is. Because the obvious relative movement exist, it is necessary to keep the lubrication of the valve base.
作者 林恺 蒋寅军
出处 《湖南电力》 2011年第4期23-26,共4页 Hunan Electric Power
关键词 球阀 动水关闭 抗振性能 水击 spherical valve dynamic closing dynamic characteristics wat~ hammer
  • 相关文献

参考文献8

  • 1GB/T144.78-1993大中型水轮机进水阀门基本技术条件[s].北京:中国标准出版社,1994. 被引量:1
  • 2GB/T18482-2001可逆式抽水蓄能机组起动试验规程[s].北京:中国标准出版社,2002. 被引量:2
  • 3DL/T709-1999压力钢管安全检测技术规程[S].北京:中国电力出版社,2000. 被引量:1
  • 4GB/T50344-2004建筑结构检测技术标准[S).北京:中国建筑工业出版社,2004. 被引量:1
  • 5GB50152-1992混凝土结构试验方法标准[S].北京:中国建筑工业出版社,1992. 被引量:30
  • 6GB50010-2002混凝土结构设计规范(s].北京:中国建筑工业出版社,2002. 被引量:1
  • 7JGJ/T8-1997建筑变形测量规程[S].北京:清华大学,1997. 被引量:1
  • 8中国工程建设标准化协会建筑振动专委会,建筑振动工程手册[M].北京:中国建筑工业出版社,2002. 被引量:1

共引文献30

同被引文献21

引证文献8

二级引证文献20

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;