摘要 电网故障时风力发电机的各种运行状态对电网稳定性的影响,特别是双馈发电机的低电压穿越问题已成为研究热点。本文根据电网故障发生及排除时,双馈感应风力发电机双PWM励磁控制器中网侧变换器的响应特性,提出一种网侧变换器低电压穿越的控制策略。该方法在电网故障发生及排除时,通过改变调制电压信号,抑制交流输入电流大幅度改变,达到稳定直流母线电压的目的。实验结果证明本文提出的方法能快速调节直流母线电压,使之趋于平稳,并且在电网故障时,使转子电能快速通过网侧变换器输送到电网。 Wind turbine's operating condition during grid fault influences grid stability.Recently low voltage ride through(LVRT) of doubly fed induction generator(DFIG) became an important research topic.A grid side converter(GSC) LVRT control method is proposed in this paper based on GSC response characteristics during the grid symmetric fault.The method modifies the modulation voltage signal during the grid fault to control the AC input current and to stabilize the DC-link voltage. The test results prove that the GSC LVRT control method would make DC-link voltage stable and convert rotor power to the grid with a fast response.
出处 《电工技术学报》 EI CSCD 北大核心 2011年第7期37-43,共7页 Transactions of China Electrotechnical Society
基金 上海市科委2010年度部分地方院校能力建设专项(10160501700) 江苏省高校自然科学研究(10KJD480004)资助项目
关键词 双馈感应风力发电机 网侧变换器 低电压穿越 直流母线电压 Doubly fed induction generator grid side converter low voltage ride through DC-link voltage