摘要
It is important for the safety of transmission system to accurately calculate single-phase earth fault current distribution.Features of double sided elimination method were illustrated.Quantitative calculation of single-phase earth fault current distribution and case verification were accomplished by using the loop method.Influences of some factors,such as single-phase earth fault location and ground resistance of poles,on short-circuit current distribution were discussed.Results show that:1) results of the loop method conform to those of double sided elimination method;2) the fault location hardly influences macro-distribution of short-circuit current.However,current near fault location is evidently influenced;and 3) the short-circuit current distribution is not so sensitive to the ground resistance of poles.
It is important for the safety of transmission system to accurately calculate single-phase earth fault current distribution. Features of double sided elimination method were illustrated. Quantitative calculation of single-phase earth fault current distribution and case verification were accomplished by using the loop method. Influences of some factors, such as single-phase earth fault location and ground resistance of poles, on short-circuit current distribution were discussed. Results show that: 1) results of the loop method conform to those of double sided elimination method; 2) the fault location hardly influences macrodistribution of short-circuit current. However, current near fault location is evidently influenced; and 3) the short-circuit current distribution is not so sensitive to the ground resistance of poles.