以三代核电技术AP1000机组为例,就某内陆核电站循环冷却水处理系统的方案优化展开讨论,从节水、阻垢、防腐、运行维护、投资等方面对所提出的三个方案进行比较,最终推荐选取循环冷却水浓缩倍率为6,只进行加药处理,冷却塔排污水直接排放的方案。
Taking the third generation PWR nuclear technique-AP1000 for example,the paper discuss the scheme optimization for circulating cooling water treatment in inland nuclear power plant.According to the aspects of water saving,scale inhibition,corrosion prevention,operation and maintenance,invest,three schemes were compared.Finally,the scheme whose cycles of concentration were 6 and only adding chemical,discharging blowdown water of cooling towers directly was commended.