期刊文献+

包含风电场的发电系统可靠性研究 被引量:22

Reliability Assessment of Generation Systems Containing Wind Farm
下载PDF
导出
摘要 风力发电对发电系统可靠性具有一定贡献,正确地估算包含风电场的发电系统可靠性有助于更好地规划电源结构。传统的单一风速模型忽略了风速与负荷之间的相关性,会给计算结果带来较大的误差。本文提出了风速的分时段估计模型,即按照风速的时间特性分别估计各个时段风速模型的参数,给出了基于此模型的包含风电场的发电系统可靠性计算的一般方法,并分析了单一风速模型与分时段风速模型之间计算结果差异产生的原因,以及风速与负荷之间的相关性对可靠性计算结果的影响。最后通过一个具体的算例说明了分析的正确性。 It is important to develop an appropriate method to estimate the reliability contribution of adding wind farm to the generation systems. However,the single wind model neglects the correlation between the wind and the load,and therefore results in great error.This paper proposes a general method to calculate the reliability of the generation system containing wind farm based on the sub-period wind model,that is,the parameters of each sub-period is calculated according to its time characteristics.Also,the reason for the difference between the single wind model and the sub-period wind model is given,together with the effect of the correlation between the wind and the load on the reliability calculation.Finally,an example is given to verify the correctness of the analysis.
作者 华文 徐政
机构地区 浙江大学电机系
出处 《高压电器》 CAS CSCD 北大核心 2010年第12期36-40,共5页 High Voltage Apparatus
关键词 风电场 可靠性 相关性 单一风速模型 分时段风速模型 wind farm reliability correlation single wind model sub-period wind model
  • 相关文献

参考文献16

二级参考文献51

共引文献346

同被引文献315

引证文献22

二级引证文献242

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部