期刊文献+

多联式空调机组室外机与环境换热的数值模拟研究 被引量:5

Numerical simulation of heat transfer between outdoor units of multi-connected split air conditioning systems and ambience
下载PDF
导出
摘要 将肋片盘管结构近似为多孔介质,应用CFD模拟方法分析了室外机与环境空气的换热过程,实验测试获得的速度和温度分布结果验证了CFD模拟方法的准确性。应用CFD模拟方法分析了不同布置方案下室外机的进风温度,得出3台室外机呈直线布置时的优化方案:相邻2台机组之间的最小距离为0.2m,机组主要进风侧与其周围高于机组的竖直壁面的极限间距为0.8m。 Treating the fin-coil structure as porous medium, analyses the heat transfer between the outdoor units and the ambience by using CFD method. Validates the accuracy of CFD simulation in terms of velocity and temperature distribution obtained by a test. Analyses the intake temperature of outdoor units under different arrangement schemes by CFD method, and obtains the optimal scheme for three units in a line, which is that the minimum separation distance between neighboring units is 0.2 m, and a vertical wall shall be apart from the unit line at least 0.8 m.
出处 《暖通空调》 北大核心 2010年第11期104-107,共4页 Heating Ventilating & Air Conditioning
关键词 空调 室外机 CFD 多孔介质 布置方案 air conditioning outdoor unit CFD porous medium arrangement scheme
  • 相关文献

参考文献9

  • 1Chow T T, Lin Z. Prediction of on-coil temperature of condensers installed at tall building re-entrant [J]. Applied Thermal Engineering, 1999, 19(2) : 117-132. 被引量:1
  • 2Chow T T, Lin Z, Wang Q W. Effect of building re-entrant shape on performance of air-cooled condensing units [J]. Energy and Buildings, 2000, 32(2) : 143-152. 被引量:1
  • 3Bojic M, Lee M, Yik F, et al. Influence of clearances on the energy performance of window-type air-conditioners at the same level outside residential buildings [J]. Building and Environment, 2002, 37(7): 713-726. 被引量:1
  • 4吴兆林,高涛,孙稚囡.高层建筑分层设置多联机室外机吸排风气流模拟及优化[J].暖通空调,2008,38(1):7-10. 被引量:17
  • 5王福军.计算流体动力学分析[M].北京:清华大学出版社,2004.126-131,147-148. 被引量:1224
  • 6Gray D D, Giorgin A. The validity of the Boussinesq approximation for liquids and gases [J]. International Journal of Heat and Mass Transfer, 1976, 19(5) : 545-551. 被引量:1
  • 7Yakhot V, Orszag S A. Renormalization group analysis of turbulence: basic theory [J]. Journal of Scientific Computing, 1986, 1(1): 3-51. 被引量:1
  • 8Vafai K. Convective flow and heat transfer in variableporosity media [J]. Journal of Fluid Mechanics, 1984, 147 (1): 233-259. 被引量:1
  • 9Amiri A, Vafai K. Analysis of dispersion effects and non- thermal equilibrium, nonDarcian, variable porosity incompressible flow through porous media [J]. International Journal of Heat and Mass Transfer, 1994, 37(6):939-954. 被引量:1

二级参考文献6

  • 1赵彬,李先庭,彦启森.暖通空调气流组织数值模拟的特殊性[J].暖通空调,2004,34(11):122-127. 被引量:36
  • 2Clifford M J, Everitt P J, Clarke R, et al. Using computational fluid dynamics as a design tool for naturally ventilated buildings[J]. Building and Environment, 1997, 32 (4): 305-312. 被引量:1
  • 3Lee M M. Application of CFD to improve the design of high rise estates[G]//HKIE Trans, 2001, 8 (1): 13-22. 被引量:1
  • 4Chen D, Lo S M, Lu W, et al. A numerical study of the effect of window configuration on the external heat and smoke spread in building fire[J]. Numerical Heat Transfer, Part A: Application, 2001, 40(3) : 821- 839. 被引量:1
  • 5Chow T T, Lin Z. Prediction of on-coil temperature of condensers installed at tall building re-entrant[J]. Applied Thermal Engineering, 1999, 19(4) : 117 - 132. 被引量:1
  • 6Chow T T, Lin Z, Wang Q W. Effect of building re-entrant shape on performance of air-cooled condensing units [J]. Energy and Buildings, 2000, 32(2): 143-152. 被引量:1