期刊文献+

谐波抑制装置中参考指令电流检测算法的研究

Study of reference instruction current detection algorithm in harmonic control device
下载PDF
导出
摘要 针对现有DFT(Discrete Fourier Transform,DFT)在非同步采样时存在的问题,提出了一种基于自适应同步抽样算法的滑窗迭代DFT谐波检测算法,该算法通过自动调整采样时间,可大大减小DFT在非同步采样时带来的计算误差。仿真结果表明该算法能实时有效地检测出负载电流中的谐波分量,并生成谐波参考指令电流作用于电力有源滤波器APF(Active Power Filter),仿真同时也表明该算法具有很好的实时性、目标跟随性和抗干扰性。 For solving the problems of DFT(Discrete Fourier Transform,DFT)in the non-synchronized sampling,this paper presents a sliding window iterative DFT algorithm based on adaptive sampling algorithm.The algorithm can reduce errors caused by the non-synchronous sampling by adjusting automatically the sampling time.The simulation results show that the algorithm can effectively detect the real-time harmonic current and generate harmonic reference instruction current of Active Power Filter.Simulation also shows the proposed algorithm has good real-time,tracing and anti-interference performances.
出处 《电子测量技术》 2010年第10期30-32,共3页 Electronic Measurement Technology
关键词 电力有源滤波器 离散傅里叶变换 谐波检测 滑窗迭代 active power filter discrete fourier transform harmonic detection sliding-window iterative