期刊文献+

典型建筑物热电冷联产系统方案优化 被引量:1

Scheme optimization of BCHP systems for typical buildings
下载PDF
导出
摘要 对应用于宾馆、医院、办公大楼3类用户的热电冷联产系统进行方案优化,得到了各用户在不同建筑面积下所对应的最优设计方案及性能指标.以净现值率为目标函数,对3类用户在不同地区的优化方案进行对比分析,宾馆的净现值率在2.1-4.1范围内变化;医院的净现值率在2.1-3.7范围内变化;办公大楼的净现值率在-0.1-1.0范围内变化.其中,宾馆用户在夏热冬暖地区的经济效益最差,医院在寒冷和夏热冬冷地区的经济效益最差,办公大楼在寒冷地区的经济效益最差. Scheme optimization of BCHP systems for three typical building(hotel,hospital and office) are conducted.The optimal design and performance index of all users under different construction area are obtained.A comparison between different regions indicates that,the best economic benefit of three typical users is in the severe cold region.The net present value rate in hotel is in the range of 2.1 to 4.1.The net present value rate in hospital is changed in the range of 2.1 to 3.7.The rate in office is changed from-0.1 to 1.0.The worst economic benefit in hotel is in the hot summer and warm winter region.The worst in hospital is in the cold region and hot summer and cold winter region.The worst in office is in the cold region.
出处 《沈阳工程学院学报(自然科学版)》 2010年第4期289-292,共4页 Journal of Shenyang Institute of Engineering:Natural Science
基金 陕西省自然科学基金资助项目(2007E236)
关键词 楼宇热电冷联产系统 逐时负荷 系统设计 性能分析 building combined cooling heating and power hourly load system design performance analysis
  • 相关文献

参考文献4

  • 1Marek Czachorski. Building load profiles and optimal CHP systems [ J ]. ASHRAB Transaction,2002,20 ( 3 ) : 682 - 690. 被引量:1
  • 2Medrano M, Brouwer J, McDonell V, et al. Integration of distributed generation systems into generic types of commercial buildings in California[ J]. Energy and Buildings,2008, 40(4) :537 -548. 被引量:1
  • 3刘爱国..我国南方地区燃气轮机分布式供能系统的研究[D].中国科学院工程热物理研究所,2009:
  • 4Ruan Y J, Liu Q R,Zhou W G, et al. Optimal option of distributed generation technologies for various commercial buildings [ J ]. Applied Energy, 2009,86 ( 9 ) : 1641 - 1653. 被引量:1