摘要
大量自然变动电源接入电网会对电网的稳定运行产生影响,通过对微网实现并网点恒定潮流控制,可大大降低自然变动电源对电网的影响。文章用光伏发电系统、柴油机发电功率跟随控制、蓄电池功率跟随控制和超级电容器功率跟随控制组成了并网点恒定潮流控制系统,提出了非线性扩散粒子群算法,以并网点潮流误差最小化为目标,将非线性扩散粒子群优化算法用于系统控制器参数设计。运用以上方法对一个实际的光伏发电微网建立了仿真平台,并以该系统某一时间段的光伏发电和本地负荷实测数据为基础对上述方法进行了并网运行仿真验证,结果表明了文章提出的恒定潮流控制及优化算法是有效的。
Connecting lots of distributed generations, which vary with natural conditions, to power grid will have unfavourable affects on the latter. By means of adopting constant power flow control for microgrid at grid-connected point can greatly reduce the affects of distributed generations that varies with natural conditions on power grid. A constant power flow control system at grid-connected point, which consists of photovoltaic (PV) system, follow-up power control of diesel generator, follow-up control of battery power and follow-up power control of super capacitor, as well as a nonlinear diffusion particle swarm optimization algorithm are proposed. Taking minimization of power flow error at grid-connected point is taken as objective, the nonlinear diffusion particle swarm optimization algorithm is used to parameter design of system controller. Using above-mentioned method, a simluation platform for an actual PV microgrid is built, and based on the PV generation data in a certain time period and the measured local load data, the simulation of grid-connected operation is performed to verify the proposed method. Simulation results show that the proposed constant power flow control method and the optimal algorithm are available.
出处
《电网技术》
EI
CSCD
北大核心
2010年第10期152-156,共5页
Power System Technology
基金
浙江省自然科学基金项目(Y107191)
浙江省重大科技专项(2009C11G2040039)
关键词
光伏微网
并网点
恒定潮流
非线性扩散粒子群优化
PV microgrid
grid-connecting point
constant power flow
non-linear diffusion particle swarm optimization