期刊文献+

空调系统中各类负荷分析与比较

Analysis and Comparison of Different Types of Exergy Loads in HVAC Systems
原文传递
导出
摘要 从概念出发分析了空调系统中的各类负荷,探讨其在多种因素影响下的变化规律。为此,以室外空气状态为参考环境,建立了各类负荷的计算公式,包括室内显热负荷、室内潜热负荷、新风显热负荷和新风潜热负荷。以长沙某办公建筑标准层为例,分析了其空调系统在夏季工况下间隙运行时的空调负荷与风冷和水冷两种情况下的负荷。结果显示,空调负荷和负荷在范围及变化趋势上存在明显差异;空调负荷的品质很低,应采用低品位能源;新风潜热负荷在空调负荷构成中最大,采用表冷器除湿将产生大量冷凝水损;室内显热负荷的峰值比室内显热负荷要推后4h;采用水冷空调系统的负荷明显低于风冷空调系统的负荷。 The exergy loads of the HVAC system are analyzed to see the variation patterns under different influencing factors. The state of outdoor air is selected as the reference state and the equations for exergy load calculations are derived, including exergy loads of sensible heat and latent heat for indoor air and fresh air, respectively. Then, different types of air conditioning loads and the corresponding exergy loads are analyzed for a standard floor of an office building in Changsha as a case study, which is equipped with an air-cooled system or a water-cooler system under the intermittent operation condition. The results show that the significant differences exist between the air conditioning loads and the exergy loads with respect to variation range and change trend. The energy quality of air-conditioning loads is very low, so it is more suitable to use low-grade energy sources to drive air conditioning systems. The exergy load of latent heat of fresh air is the highest in all exergy loads because of its large amount of exergy destruction of condensed water. The maximum indoor exergy load of sensible heat is observed 4 hours later than its air conditioning part. Moreover, the exergy loads in the water-cooled system are considerably less than those in the air-cooled system.
作者 王厉 李念平
出处 《科技导报》 CAS CSCD 北大核心 2010年第16期87-91,共5页 Science & Technology Review
基金 国家自然科学基金项目(50878078)
关键词 空调系统 分析 负荷 空调负荷 HVAC system exergy analysis exergy load air conditioning load
  • 相关文献

参考文献14

  • 1Kano(g)lu M,(C)arpinlio(g)lu M(O),Yildirim M.Energy and exergy analysis of an experimental open-cycle desiccant cooling system[J].Applied Thermal Engineering,2004,24(5-6):919-932. 被引量:1
  • 2Wang S,Morimoto M,Haruo S,et al.Evaluating the low exergy of chilled water in a radiant cooling system[J].Energy and Buildings,2008,40(10):1856-1865. 被引量:1
  • 3李廷贤,刘艳华.低温热水地板辐射采暖的分析[J].节能技术,2004,22(4):16-17. 被引量:7
  • 4Wei Z,Zmeureanu R.Exergy analysis of variable air volume systems for an office building[J].Energy Conversion and Management,2009,50(2):387-392. 被引量:1
  • 5Heidarinejad G,Karami M,Delfani S.Numerical simulation of counterflow wet-cooling towers[J].International Journal of Refrigeration,2009,32(5):996-1002. 被引量:1
  • 6Milosavljevic N,Heikkil(a)P.A comprehensive approach to cooling tower design[J].Applied Thermal Engineering,2001,21(9):899-915. 被引量:1
  • 7颜志猛,连之伟,王文.一次回风空调系统的分析[J].流体机械,2002,30(11):58-60. 被引量:5
  • 8Balta M T,Kalinci Y,Hepbasli A.Evaluating a low exergy heating system from the power plant through the heat pump to the building envelope[J].Energy and Buildings,2008,40(10):1799-1804. 被引量:1
  • 9Asada H,Boelman E C.Exergy analysis of a low temperature radiant heating system[J].Building Services Engineering Research & Technology,2004,25(3):197-209. 被引量:1
  • 10李震,江亿,刘晓华,谢晓云.湿空气处理的分析[J].暖通空调,2005,35(1):97-102. 被引量:15

二级参考文献26

  • 1BrodjanskijBM 王加旋 译.炯方法及其应用[M].北京:中国电力出版社,1996.. 被引量:1
  • 2CammarataG, Fichera A, Mammino L, et al.Exergonomic optimization of an air-conditioning system. Journal of Energy Resources Technology,1997,119(2) : 62 - 69. 被引量:1
  • 3Fratzscher W. Exergy and possible applications. Rev Gen Therm, 1997,36 : 690 - 696. 被引量:1
  • 4San J Y. Exergy analysis of desiccant cooling systems:[Ph D Thesis]. Illinois: Illinois Institute of Technology,1985. 被引量:1
  • 5Wepfer W J, Gaggioli R A, Obert E F. Proper evaluation of available energy for HVAC. In: ASHRAE Trans.1979,85(1). 214 - 230. 被引量:1
  • 6Ahrendts J. Reference states. Energy, 1980,5 (8 - 9) :667 - 677. 被引量:1
  • 7Szargut J D, Styrylska T. Die Exergetische Analyse von Prozenssen der feuchten Luft. Heiz Luft Haustech,1969,20:173 - 178. 被引量:1
  • 8Szargut J. International progress in second law analysis.Energy, 1979,5(8- 9):709- 718. 被引量:1
  • 9Kameyama H, Yoshida K, Yarmuchi S, et al. Evaluation of reference exergies for the elements. Applied Energy,1982,11(1) :69 - 83. 被引量:1
  • 10Moran M J. Availability Analysis: A Cuide to Efficient Use New York: ASME Press, 1989. 被引量:1

共引文献22

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部