期刊文献+

炉水泵电机运行温度高故障的治理 被引量:4

Treatment for extra high operation temperature of motor of water circulating pump
下载PDF
导出
摘要 在多次出现炉水泵电机运行温度高和解体检修的情况下,分析发生问题的主要原因是炉水泵电机腔内进入污物,采取在泵底加装排污管阀定期排污和在电机内循环冷却水系统中加装外置过滤器收集污物,并定期清洗过滤器等措施,效果良好。 After existing many times extra high operation temperature,the motor of water circulating pump was disassembled for maintenance.Dirt in furnace chamber is the main cause for the problem.Sewerage pipe velvets were added to the pump bottom for periodic blowdown and outside filters were installed in inner circulating cooling water system to collect dirt.Other measures such as periodic cleaning filters were also implemented and the results were positive.
出处 《湖南电力》 2010年第3期29-31,36,共4页 Hunan Electric Power
关键词 炉水泵电机 污物 温度 boiler water circulating pump motor dirt
  • 相关文献

参考文献4

  • 1德国KSB公司循环泵LUVAK250-300/1使用手册[Z].2007. 被引量:1
  • 2哈尔滨锅炉厂 2×600 MW超临界锅炉说明书及图纸资料[Z].2007. 被引量:1
  • 3益阳发电有限公司防止污物进入炉水泵处理方案[R].2009. 被引量:1
  • 4DL/T1132-2009,电站炉水循环泵电机检修导则[S].北京:中国标准出版社. 被引量:1