期刊文献+

固定串补电容对工频故障分量继电保护的影响 被引量:12

THE EFFECT OF FIXED SERIES CAPACITOR ON FAULT COMPONENT PROTECTIVE RELAYING
下载PDF
导出
摘要 固定串补电容对工频故障分量继电保护有一定的影响。按K(Zzd-Xc)整定保护范围时,故障分量距离元件可用于快速切除近端故障,对于远区故障,拒动、误动均有可能。当串补电容的容抗小于系统电源的正序阻抗(含短路点至电源的正序线路阻抗)时,故障分量方向继电器可用于串补线路。 Fixed series capacitor (FSC ) has some effects on fault component protective relaying. The fault component distance relay can be used to trip close fault rapidly when its protection range is set with K (Zzd-Xc). however. In the case of remote fault. its operation is indefinite. The study shows that if the capacitive reactance of fixed series capacitor is less than the system power source's positive sequence impedance. the fault component direction relay can be used in line with FSC.
出处 《电力系统自动化》 EI CSCD 北大核心 1998年第12期31-33,共3页 Automation of Electric Power Systems
基金 国家自然科学基金!资助项目(59637050)
关键词 固定串补电容 故障分量 继电保护 电力系统 fixed series capacitor fault component distance relay fault component direction relay
  • 相关文献

参考文献7

二级参考文献5

共引文献43

同被引文献79

引证文献12

二级引证文献65

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部